| Complementary |
| fixing mode | Plastic compression spring |
| Average resistance | 848 Ohm network: DC at 23 °C +/- 10 % |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC |
| [Ie] rated operational current | 6 A 1 C/O (AC-1/DC-1) conforming to IEC/UL |
| minimum switching current | 100 mA |
| Minimum switching voltage | 12 V |
| [Ui] rated insulation voltage | 250 V conforming to IEC; 277 V conforming to cUL |
| Minimum switching capacity | 120 mW |
| Maximum switching voltage | 277 V |
| Drop-out voltage threshold | >= 0.05 Uc |
| Load current | 6 A at 250 V AC 0.5 mm mounting distance |
| Electrical durability | 60000 cycles for resistive load, 6 A at 250 V, AC-1 |
| Maximum switching capacity | 1500 VA; 150 W |
| Operating time | 5 ms reset; 12 ms |
| Terminals description ISO n°1 | (A1-A2)CO; (11-12-14)OC |
| Average coil consumption | 0.17 W, DC |
| Mechanical durability | 10000000 cycles |
| Safety reliability data | B10d = 60000 |
| Control type | Without lockable test button |
| Compatibility code | RSL |
| Contact terminal arrangement | Separate |
| Connections - terminals | Spring terminals, 1 x 0.2...1 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Spring terminals, 1 x 0.2...1 x 1.5 mm² (24 AWG...16 AWG) solid without cable end |
| Clamping force | 10…40 N |
| Protection category | RT III |
| Mounting support | 35 mm symmetrical DIN rail |
| Operating position | Any position |
| Test levels | Level A group mounting |
| Device presentation | Complete product |
| Sale per indivisible quantity | 10 |
| Contacts material | Silver alloy (AgSnO2) |
| Shape of pin | Flat (PCB type) |
| Width | 6.2 mm |
| Height | 78.6 mm |
| Depth | 101 mm |
| Net weight | 0.029 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Input voltage | 12 V AC/DC (input voltage limit: 11.4...14.4 V) |
| Dielectric strength | 1000 V AC between contacts; 4000 V AC between coil and contact |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Ambient air temperature for operation | -40…55 °C |
| Standards | CSA C22.2 No 14; UL 508; IEC 61810-1 |
| Product certifications | CSA; UL; GOST |
| Marking | CE |
| Ambient air temperature for storage | -40…85 °C |
| Vibration resistance | 10 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles not operating conforming to IEC 60068-2-6; 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)10 cycles in operation conforming to IEC 60068-2-6 |
| Shock resistance | 10 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Harmony Electromechanical Relays |
| Series name | RSL series |
| Product or component type | Pre-assembled plug-in relay with socket |
| Relay type | Slim interface relay |
| Contact operation | Standard |
| Contacts type and composition | 1 C/O |
| status LED | With |
| [Uc] control circuit voltage | 12 V AC/DC |
| [Ithe] conventional enclosed thermal current | 6 A at -40…55 °C |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.5 cm |
| Package 1 Width | 7 cm |
| Package 1 Length | 10.7 cm |
| Package 1 Weight | 31 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 8.5 cm |
| Package 2 Width | 7 cm |
| Package 2 Length | 10.7 cm |
| Package 2 Weight | 315 g |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 300 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 9.968 kg |
Harmony Relay. Pre-assembled narrow interface relay RSL. Relay with 1 changeover contact, standard contact. Control voltage 12 VAC/DC. Contact loadable up to 6 A. Width 6.2 mm. Connections spring-loaded terminals, comb rails available. LED display, voltage adjustment and protection integrated in the base. Lever for easy insertion and removal of the relay. Holder on the base for label. Base can be snapped onto a top hat rail. The relay is already plugged into the base and can be installed immediately.