| Complementary |
| Average resistance | 350 Ohm network: AC at 20 °C +/- 15 % |
| [Ue] rated operational voltage | 19.2...26.4 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 3.6 kV conforming to IEC 61000-4-5 |
| [Ie] rated operational current | 12 A (AC-1/DC-1) NO conforming to IEC; 6 A (AC-1/DC-1) NC conforming to IEC |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60947 |
| Maximum switching voltage | 300 V DC conforming to IEC |
| Drop-out voltage threshold | >= 0.15 Uc AC |
| Load current | 12 A at 250 V AC; 12 A at 28 V DC |
| minimum switching current | 10 mA |
| Maximum switching capacity | 3000 VA AC; 336 W DC |
| minimum switching voltage | 12 V |
| Minimum switching capacity | 120 mW at 10 mA, 12 V |
| Operating time | 20 ms operating; 20 ms reset |
| Mechanical durability | 10000000 cycles |
| Electrical durability | 100000 cycles, 12 A at 250 V, AC-1 NO; 100000 cycles, 6 A at 250 V, DC-1 NC |
| Safety reliability data | B10d = 100000 |
| Average coil consumption | 0.75 VA AC |
| Contact terminal arrangement | Separate |
| Connections - terminals | Connector, 1 x 0.25...1 x 2.5 mm² (22 AWG...14 AWG) flexible with cable end; Connector, 2 x 0.25...2 x 1 mm² (22 AWG...17 AWG) flexible with cable end; Connector, 1 x 0.5...1 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Connector, 2 x 0.5...2 x 1.5 mm² (20 AWG...16 AWG) solid without cable end |
| torque value | 0.8 N.m; 0.8 N.m |
| Protection category | RT I |
| Operating position | Any position |
| Test levels | Level A group mounting |
| Device presentation | Complete product |
| Sale per indivisible quantity | 30 |
| Contacts material | Silver alloy (AgNi) |
| Shape of pin | Flat (PCB type) |
| Net weight | 0.050 kg |
| Compatibility code | RSB |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Dielectric strength | 1000 V AC between contacts; 5000 V AC between coil and contact |
| Vibration resistance | +/- 1 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -40…70 °C (AC) |
| Standards | IEC 61810-1; CSA C22.2 No 14; UL 508; IEC 61984 |
| Product certifications | CE; UL; CSA; EAC |
| Ambient air temperature for storage | -40…85 °C |
| Shock resistance | 10 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Electromechanical Relays |
| Series name | RSB series |
| Product or component type | Pre-assembled plug-in relay with socket |
| Relay type | Interface relay |
| Contacts type and composition | 1 C/O |
| Contact operation | Standard |
| status LED | With |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Control type | Without lockable test button |
| [Ithe] conventional enclosed thermal current | 12 A at -40…40 °C |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.420 cm |
| Package 1 Width | 1.560 cm |
| Package 1 Length | 6.420 cm |
| Package 1 Weight | 53.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 8.500 cm |
| Package 2 Width | 18.500 cm |
| Package 2 Length | 27.000 cm |
| Package 2 Weight | 1.777 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 180 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 11.525 kg |
Harmony Relay. Pre-assembled and ready-to-use interface relay RSB consisting of relay, base, protection module with LED display, retaining bracket and label. Number of contacts - 1, design - relay changeover contact, contact load capacity - 12 A. Coil control voltage - 24 VAC. Plug-in base with screw terminals in separate arrangement for mounting on top hat rail or screwable onto mounting plate. Protection module - varistor. Plastic retaining bracket for fixing and easy removal of the relay. Label for identification. All components are assembled ready for use and the pre-assembled relay can be used immediately.