Schneider Electric RMPT1UUBD, EAN: 3606487614159

Schneider Electric RMPT1UUBD signal conditioner RTD Pt100 Pt1000

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Schneider Electric RMPT1UUBD signal conditioner RTD Pt100 Pt1000

Lieske Part No. 893213
Mfg Part No RMPT1UUBD
EAN-Code 3606487614159
Manufacturer Schneider Electric
Here only 173,38 EUR
206,32 EUR incl. VAT

Further information for Schneider Electric RMPT1UUBD signal conditioner RTD Pt100 Pt1000

Complementary
Protection typeReverse polarity protection on power supply; Overvoltage protection on output; Short-circuit protection on output
[Us] rated supply voltage24 V DC +30 %...-25 %, isolated
Measurement error+/- 0.1 % of full scale
Repeat accuracy+/- 0.03 %
Clamping connection capacity20...14 AWG
Tightening torque0.4…0.5 N.m; 0.4…0.5 N.m
MarkingCULus; DNV; CE; UKCA; WEEE; China RoHS
Surge withstand1 kV during 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage300 V
Fixing modeClip-on (35 mm DIN rail)
Safety reliability dataMTTFd = 297.8 years; B10d = 274817
Net weight0.07 kg
Temperature coefficient< 100 ppm/°C
Wire stripping length8…9 mm
Status LED3 LEDs (green) PWR (Power Status); (red) high signal level; (red) low signal level
Overvoltage categoryII
Width6.2 mm
Height110 mm
Depth110 mm
Relative humidity5…95 %
Contractual warranty
Warranty (in months)18
Environment
Product certificationscULus; DNV
IP degree of protectionIP20
Shock resistance50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance5 gn (f= 10…150 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge6 kV (in contact) conforming to IEC 61000-4-2; 8 kV (in air) conforming to IEC 61000-4-2
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-40…70 °C
Pollution degree2 conforming to IEC 60664-1
Operating altitude0...2000 m
Electromagnetic emissionConducted emissions conforming to CISPR 11; Radiated emissions conforming to CISPR 11
Dielectric strength3 kV AC between the inputs and the supply circuit; 3 kV AC between the outputs and the supply circuit; 3 kV AC between input and output
Logistical informations
Country of originCN
Main
Range of productHarmony Analog
Product or component typeSignal conditioner
Analogue input typeRTD -200...+850 °C
Analogue output typeCurrent 0...20 mA = 10 kOhm; Voltage 0...5 V >= 10 kOhm; Voltage 1...5 V >= 10 kOhm
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.300 cm
Package 1 Width11.800 cm
Package 1 Length12.000 cm
Package 1 Weight101.000 g
Unit Type of Package 2S02
Number of Units in Package 230
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight3.459 kg
Die Signalwandler der Baureihe Harmony Analog sind analoge Messumformer zur nahtlosen Integration in Industrielle Automatisierungs- und Prozesssteuerungssysteme. Dieser Signalwandler dient zur Umwandlung von Temperatursignalen aus RTD-Messungen in ein isoliertes Analogsignal. Dabei unterstützt er mehrere RTD-Typen, darunter Pt100, Pt1000, Cu50 und Cu100. Mit seinem ultrakompakten Design von 6,2 mm und dem einfachen Zugang zur Verdrahtung vereinfacht der RMPT1UUBD die Installation, Inbetriebnahme und Fehlerbehebung und eignet sich somit ideal für Schaltschränke und industrielle Umgebungen. Aufgrund der Vielzahl von vorhandenen Produktstandards und Zertifizierungen geeignet für den internationalen Einsatz. Zudem können Sie detaillierte Informationen zu Materialinhalten, Umweltauswirkungen und Kreislaufwirtschaft erhalten, die Ihre Nachhaltigkeitsziele unterstützen.