| Complementary |
| Protection type | Reverse polarity protection on power supply; Overvoltage protection on output; Short-circuit protection on output |
| [Us] rated supply voltage | 24 V DC +30 %...-25 %, isolated |
| Measurement error | +/- 0.1 % of full scale |
| Repeat accuracy | +/- 0.03 % |
| Temperature coefficient | < 100 ppm/°C |
| Clamping connection capacity | 20...14 AWG |
| Tightening torque | 0.4…0.5 N.m; 0.4…0.5 N.m |
| Marking | CULus; DNV; CE; UKCA; WEEE; China RoHS |
| IP degree of protection | IP20 |
| Surge withstand | 1 kV during 1.2/50 µs conforming to IEC 61000-4-5 |
| [Ui] rated insulation voltage | 300 V |
| Fixing mode | Clip-on (35 mm DIN rail) |
| Safety reliability data | MTTFd = 241.9 years; B10d = 223265 |
| Net weight | 0.07 kg |
| Wire stripping length | 8…9 mm |
| Status LED | 3 LEDs (green) PWR (Power Status); (red) high signal level; (red) low signal level |
| Overvoltage category | II |
| Operating altitude | 0...2000 m |
| Width | 6.2 mm |
| Height | 110 mm |
| Depth | 110 mm |
| Relative humidity | 5…95 % |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Product certifications | cULus; DNV |
| Shock resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
| Vibration resistance | 5 gn (f= 10…150 Hz) conforming to IEC 60068-2-6 |
| Resistance to electrostatic discharge | 6 kV (in contact) conforming to IEC 61000-4-2; 8 kV (in air) conforming to IEC 61000-4-2 |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -40…70 °C mounting side by side |
| Pollution degree | 2 conforming to IEC 60664-1 |
| Electromagnetic emission | Conducted emissions conforming to CISPR 11; Radiated emissions conforming to CISPR 11 |
| Dielectric strength | 3 kV AC between the inputs and the supply circuit; between the outputs and the supply circuit; between input and output |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range of product | Harmony Analog |
| Product or component type | Signal conditioner |
| Analogue input type | Current 0...20 mA; Current 4...20 mA; Voltage 0...10 V DC; Voltage 2...10 V DC; Voltage 0...5 V DC; Voltage 1...5 V DC |
| Analogue output type | Current 0...20 mA = 10 kOhm; Voltage 0...5 V >= 10 kOhm; Voltage 1...5 V >= 10 kOhm |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.400 cm |
| Package 1 Width | 11.800 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 102.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.501 kg |
Die Signalwandler der Baureihe Harmony Analog sind analoge Messumformer zur nahtlosen Integration in Industrielle Automatisierungs- und Prozesssteuerungssysteme. Dieser universelle Signalwandler wandelt ein analoges Signal von 0(1)-5V oder 0(2)-10V oder 0(4)-20mA um und vervielfacht es. Mit seinem ultrakompakten Design von 6,2 mm und dem einfachen Zugang zur Verdrahtung vereinfacht der RMC2UUBD die Installation, Inbetriebnahme und Fehlerbehebung und eignet sich somit ideal für Schaltschränke und industrielle Umgebungen. Aufgrund der Vielzahl von vorhandenen Produktstandards und Zertifizierungen geeignet für den internationalen Einsatz. Zudem können Sie detaillierte Informationen zu Materialinhalten, Umweltauswirkungen und Kreislaufwirtschaft erhalten, die Ihre Nachhaltigkeitsziele unterstützen.