Schneider Electric RMC2UUBD, EAN: 3606487614142

Schneider Electric RMC2UUBD signal conditioner U/I Harmony

Industrial Material > Automation > Frequency converter, soft starter

Schneider Electric RMC2UUBD signal conditioner U/I Harmony

Lieske Part No. 894606
Mfg Part No RMC2UUBD
EAN-Code 3606487614142
Manufacturer Schneider Electric
Here only 238,45 EUR
283,76 EUR incl. VAT

Further information for Schneider Electric RMC2UUBD signal conditioner U/I Harmony

Complementary
Protection typeReverse polarity protection on power supply; Overvoltage protection on output; Short-circuit protection on output
[Us] rated supply voltage24 V DC +30 %...-25 %, isolated
Measurement error+/- 0.1 % of full scale
Repeat accuracy+/- 0.03 %
Temperature coefficient< 100 ppm/°C
Clamping connection capacity20...14 AWG
Tightening torque0.4…0.5 N.m; 0.4…0.5 N.m
MarkingCULus; DNV; CE; UKCA; WEEE; China RoHS
IP degree of protectionIP20
Surge withstand1 kV during 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage300 V
Fixing modeClip-on (35 mm DIN rail)
Safety reliability dataMTTFd = 241.9 years; B10d = 223265
Net weight0.07 kg
Wire stripping length8…9 mm
Status LED3 LEDs (green) PWR (Power Status); (red) high signal level; (red) low signal level
Overvoltage categoryII
Operating altitude0...2000 m
Width6.2 mm
Height110 mm
Depth110 mm
Relative humidity5…95 %
Contractual warranty
Warranty (in months)18
Environment
Product certificationscULus; DNV
Shock resistance50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance5 gn (f= 10…150 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge6 kV (in contact) conforming to IEC 61000-4-2; 8 kV (in air) conforming to IEC 61000-4-2
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-40…70 °C mounting side by side
Pollution degree2 conforming to IEC 60664-1
Electromagnetic emissionConducted emissions conforming to CISPR 11; Radiated emissions conforming to CISPR 11
Dielectric strength3 kV AC between the inputs and the supply circuit; between the outputs and the supply circuit; between input and output
Logistical informations
Country of originCN
Main
Range of productHarmony Analog
Product or component typeSignal conditioner
Analogue input typeCurrent 0...20 mA; Current 4...20 mA; Voltage 0...10 V DC; Voltage 2...10 V DC; Voltage 0...5 V DC; Voltage 1...5 V DC
Analogue output typeCurrent 0...20 mA = 10 kOhm; Voltage 0...5 V >= 10 kOhm; Voltage 1...5 V >= 10 kOhm
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.400 cm
Package 1 Width11.800 cm
Package 1 Length12.000 cm
Package 1 Weight102.000 g
Unit Type of Package 2S02
Number of Units in Package 230
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight3.501 kg
Die Signalwandler der Baureihe Harmony Analog sind analoge Messumformer zur nahtlosen Integration in Industrielle Automatisierungs- und Prozesssteuerungssysteme. Dieser universelle Signalwandler wandelt ein analoges Signal von 0(1)-5V oder 0(2)-10V oder 0(4)-20mA um und vervielfacht es. Mit seinem ultrakompakten Design von 6,2 mm und dem einfachen Zugang zur Verdrahtung vereinfacht der RMC2UUBD die Installation, Inbetriebnahme und Fehlerbehebung und eignet sich somit ideal für Schaltschränke und industrielle Umgebungen. Aufgrund der Vielzahl von vorhandenen Produktstandards und Zertifizierungen geeignet für den internationalen Einsatz. Zudem können Sie detaillierte Informationen zu Materialinhalten, Umweltauswirkungen und Kreislaufwirtschaft erhalten, die Ihre Nachhaltigkeitsziele unterstützen.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/894606
qrcode für Schneider Electric RMC2UUBD signal conditioner U/I Harmony