| Complementary |
| [Us] rated supply voltage | self-powered |
| Supply voltage limits | 194…528 V AC, 3 phases |
| Supply frequency | 50/60 Hz +/- 10 % |
| Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
| Measurement range | 220...480 V AC |
| Measurement voltage limits | 176…528 V AC |
| Voltage detection threshold | < 194 V |
| Maximum measuring cycle | 140 ms measurement cycle as true rms value |
| Threshold adjustment voltage | 2...20 % of Un selected; -12...-2 % in the range 220 V AC; +2...+10 % in the range 480 V AC |
| Hysteresis | 2 % |
| Adjustment of asymmetry threshold | 5...15 % of Un selected |
| Measurement error | < 1 % over the whole range with voltage variation; 0.05 %/°C with temperature variation |
| Time delay type | Adjustable 0.1...10 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms at 480 V |
| Response time | < 200 ms (in the event of a fault) |
| Output contacts | 2 C/O |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC; 5 A DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Control circuit voltage limits | - 12 % + 10 % Un |
| Control circuit frequency | 50...60 Hz +/- 10 % |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to IEC 61000-6-2 |
| Standards | IEC 60255-1 |
| Product certifications | GL; UL; CSA; GOST; C-Tick |
| Marking | CE |
| Directives | 89/336/EEC - electromagnetic compatibility; 73/23/EEC - low voltage directive |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON; LED (yellow) for relay ON; LED (yellow) for fault |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 399.5 years; B10d = 360000 |
| Height | 90 mm; 88.9 mm |
| Width | 35 mm; 35.6 mm |
| Depth | 72 mm; 71.1 mm |
| Net weight | 0.12 kg; 0.12 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Multifunction control relay |
| Product or component type | 3-phase control relay |
| Relay name | RM35TF |
| Relay monitored parameters | Undervoltage and overvoltage in window mode; Phase sequence; Phase failure detection; Asymmetry |
| Control type | Without test button |
| Contacts type and composition | 2 C/O |
| [Uc] control circuit voltage | 220...480 V |
| Product specific application | For 3-phase supply |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.800 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 9.700 cm |
| Package 1 Weight | 131.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.070 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 64.124 kg |
Harmony Control. This network monitoring relay monitors three-phase networks (220-480 VAC in 6 stages) for phase sequence, phase failure, phase asymmetry (5-15%), overvoltage and undervoltage in window mode (-20--2%/+2-+20% depending on voltage). Two relay changeover switches are available for reporting, which can handle up to 5 A. The limit value can be set for the asymmetry, undervoltage and overvoltage range and a switch-off delay can be set for the output. The settings are made using controls on the front, which can be protected against changes under a transparent cover. Three LEDs show the status. The width is 35 mm and it is mounted on the top hat rail. The cable is connected using screw terminals.