| Complementary |
| [Us] rated supply voltage | 380...415 V AC 50/60 Hz, non self-powered |
| Supply voltage limits | 323…456.5 V AC |
| Maximum power consumption in VA | 8 VA |
| Measurement range | 150 mA...15 A AC 50/60 Hz |
| Maximum measuring cycle | 100 ms measurement cycle as true rms value |
| Hysteresis | 5…50 % adjustable of threshold setting; 3 % fixed of full scale for window mode |
| Setting accuracy of the switching threshold | +/- 10 % of the full scale; +/- 20 % of the full scale |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 2 % for time delay |
| Measurement error | < 1 % over the whole range with voltage variation; 0.05 %/°C with temperature variation |
| Time delay type | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms at maximum voltage |
| Power on Delay | 300 ms |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| operating voltage tolerance | - 15 % + 10 % Un |
| Resistance across terminals | 0.005 Ohm at E3-M terminals; 0.015 Ohm at E2-M terminals; 0.05 Ohm at E1-M terminals |
| Threshold setting | 10...100 % |
| Insulation | Between supply and measurement |
| Contacts material | Cadmium free |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60255-1 |
| Product certifications | CCC; EAC; CSA; RCM; UL; GL; CE |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz; -20…60 °C at 50 Hz |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529; IP30 (housing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) for relay ON; LED (green) for power ON |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 296.8 years; B10d = 270000 |
| Height | 90 mm; 88.9 mm |
| Width | 35 mm; 35.6 mm |
| Depth | 73 mm; 73.7 mm |
| Net weight | 0.12 kg; 0.12 kg |
| Environmental characteristic | 3K3 C |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Current control relay |
| Product or component type | Current control relay |
| Relay name | RM35JA |
| Relay monitored parameters | Overcurrent or undercurrent detection; Overcurrent or undercurrent in window mode |
| Control type | With test button |
| Contacts type and composition | 2 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.8 cm |
| Package 1 Width | 4.5 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 129 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.532 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 640 |
| Package 3 Height | 75 cm |
| Package 3 Width | 40 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 107.56 kg |
Harmony Control. This current monitoring relay monitors a conductor for exceedance or undershoot of the set limit value (1.5-15 A). You can choose between exceedance, undershoot and overshoot and undershoot in window mode. An error memory is optionally available, which holds the error message until a reset. Two relay changeover switches are available for reporting, which can be loaded up to 8 A. The mode of operation, the limit value, the switching hysteresis and a drop-out delay can be set. The settings are made using control elements on the front, which can be protected against changes under a transparent cover. An illuminated scale arrow makes it very easy to see the setting of the potentiometers, even from a distance. The diagnostic switch on the front enables the output relays to be switched off to test the entire application. When the transparent cover is closed, the diagnostic switch is automatically reset. The supply voltage is 380-415 VAC. Two LEDs show the status. The width is 35 mm and it is mounted on a top hat rail. The cable connection is made via screw terminals.