| Complementary |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| Maximum power consumption in VA | 3.5 VA AC |
| Maximum power consumption in W | 0.6 W DC |
| Measurement range | 2...500 mA AC/DC E2-M terminals |
| Maximum measuring cycle | 30 ms measurement cycle as true rms value |
| Hysteresis | 5…50 % of threshold setting |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 2 % for time delay |
| Measurement error | 0.05 %/°C with temperature variation; 1 by volt over the whole range with voltage variation |
| Time delay type | Adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault; Adjustable 1...20 s, 0 + 10 % Ti- inhibition time delay upon startup |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms time delay |
| Power on Delay | 300 ms |
| Output contacts | 2 C/O |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| operating voltage tolerance | - 15 % + 10 % Un |
| Control circuit frequency | 40...70 Hz +/- 10 % |
| Resistance across terminals | 1 Ohm at E2-M terminals; 5 Ohm at E1-M terminals; 0.2 Ohm at E3-M terminals |
| Measurement accuracy | +/- 10 % of the full scale value |
| Threshold setting | 10...100 % |
| Insulation | Between supply and measurement |
| Contacts material | Cadmium free |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | GL; CSA; GOST; UL; C-Tick |
| Marking | CE : EMC 89/336/EEC; CE : 73/23/EEC |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON; LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 296.8 years; B10d = 270000 |
| Height | 90 mm; 88.9 mm |
| Width | 35 mm; 35.6 mm |
| Depth | 72 mm; 71.1 mm |
| Net weight | 0.13 kg; 0.13 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Current control relay |
| Product or component type | Current control relay |
| Relay name | RM35JA |
| Relay monitored parameters | Overcurrent and undercurrent control |
| Control type | Without test button |
| Contacts type and composition | 2 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 138.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.350 kg |
Harmony Control. This current monitoring relay monitors a conductor for exceedance or undershoot of the set limit value in the range 2-500 mA. Two relay changeover switches are available for reporting, which can be loaded up to 5 A. The mode of operation, the limit value, the switching hysteresis and a drop-out delay are adjustable. The settings are made using control elements on the front, which can be protected against changes under a transparent cover. The width is 35 mm and it is mounted on the top hat rail. The wide-voltage power supply 24-240 VAC/DC (50-60 Hz) enables universal use. The cable connection is made using screw terminals.