| Complementary |
| Reset time | 2000 ms |
| Maximum switching voltage | 250 V AC/DC |
| [Un] rated nominal voltage | 208...480 V AC 50/60 Hz, non self-powered; 230 V AC 50/60 Hz, non self-powered |
| Supply voltage limits | 183…528 V AC |
| operating voltage tolerance | - 15 % + 10 % Un |
| Resistance across terminals | 0.01 Ohm at E1-L2 terminals |
| Width | 35 mm |
| Output contacts | 1 C/O |
| nominal output current | 5 A |
| Maximum measuring cycle | 140 ms as true rms value |
| delay at power up | 0.5 s |
| Hysteresis | 5 % of threshold |
| Measurement accuracy | +/- 10 % of the full scale value |
| Repeat accuracy | +/- 1 % for input and measurement circuit; +/- 1 % for time delay |
| Measurement error | 1 % by volt over the whole range; +/- 0.05 %/°C |
| Response time | < 300 ms (in the event of a fault) |
| overload input current | 11 A permanent at 25 °C E1-L2 terminals; 50 A non repetitive < 1 s at 25 °C E1-L2 terminals |
| Marking | CE : EMC 89/336/EEC; CE : 73/23/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5; > 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1; > 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5; > 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1; > 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5; > 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Supply frequency | 50/60 Hz +/- 10 % |
| Operating position | Any position |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Status LED | 1 LED green for power ON; 1 LED yellow for fault; 1 LED yellow for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Control type | Without test button |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 500 ms |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | C-Tick; CSA; GOST; UL; GL |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1; 1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric strength | 2 kV AC 50 Hz (shock wave 4 kV) |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Pump control relays |
| Product or component type | Pump control relay |
| Product specific application | For 3-phase and single-phase pump |
| Relay name | RM35BA |
| Relay monitored parameters | Overcurrent and undercurrent control; Phase sequence on 3-phase supply; Phase failure on 3-phase supply |
| Time delay type | Adjustable 1...60 s, +/- 10 % Ti- inhibition time delay upon startup; Adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC/DC |
| Maximum power consumption in VA | 5 VA AC |
| Measurement range | 1...10 A; 208...480 V AC |
| Utilisation category | AC-12 conforming to IEC 60947-5-1; AC-13 conforming to IEC 60947-5-1; AC-14 conforming to IEC 60947-5-1; AC-15 conforming to IEC 60947-5-1; DC-12 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.0 cm |
| Package 1 Width | 4.6 cm |
| Package 1 Length | 9.7 cm |
| Package 1 Weight | 123.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 6.526 kg |
Harmony Control. This monitoring relay is used to control and monitor pumps in single-phase and three-phase networks. In single-phase networks (230 VAC), monitoring for overcurrent and undercurrent is carried out using true RMS measurement and in three-phase networks (208-480 VAC) monitoring for phase sequence and phase failure is also carried out. The device can be used to control pumps for monitoring or for 2-point control of a fill level, for which the corresponding control inputs are available.