| Complementary |
| [Us] rated supply voltage | 110...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 60…280 V AC |
| Power consumption in VA | 5 VA AC |
| Measurement range | 80...300 V AC/DC |
| Maximum measuring cycle | 250 ms measurement cycle as true rms value |
| Hysteresis | 5 % fixed of threshold setting |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 2 % for time delay |
| Measurement error | < 1 % over the whole range with voltage variation |
| Time delay type | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms at maximum voltage |
| Power on delay | 600 ms |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Contacts material | Cadmium free |
| Maximum power consumption in W | 2 W DC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60255-1 |
| Product certifications | CCC; CE; CSA; EAC; UL; GL; RCM |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz; -20…60 °C at 50 Hz |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
| Insulation resistance | > 100 MOhm at 500 V DC |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 433.7 years; B10d = 400000 |
| Height | 90 mm; 88.9 mm |
| Width | 22.5 mm; 22.9 mm |
| Depth | 73 mm; 73.7 mm |
| Net weight | 0.09 kg; 0.09 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Voltage control relay |
| Product or component type | Voltage control relay |
| Relay name | RM22UA |
| Relay monitored parameters | Overvoltage and undervoltage detection |
| Control type | With test button |
| Contacts type and composition | 2 C/O |
| Network number of phases | 1 phase |
| Supply circuit type | AC/DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.6 cm |
| Package 1 Width | 8.2 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 104.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 4.58 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 640 |
| Package 3 Height | 80.0 cm |
| Package 3 Width | 80.0 cm |
| Package 3 Length | 60.0 cm |
| Package 3 Weight | 86.18 kg |
Harmony Control. This voltage monitoring relay monitors a measuring circuit for exceedance or undershoot of the set limit value (80-300 VAC/DC). Two relay changeovers are available for reporting, which can be loaded up to 8 A. A limit value and the response or drop-out delay can be set for each exceedance or undershoot. The settings are made using control elements on the front, which can be protected against changes under a transparent cover. An illuminated scale arrow makes it very easy to see the setting of the potentiometers, even from a distance. The diagnostic switch on the front enables the output relays to be switched off to test the entire application. When the transparent cover is closed, the diagnostic switch is automatically reset. The device is powered from the measuring circuit. Two LEDs show the status. The width is 22.5 mm and it is mounted on a top hat rail. The cable is connected using screw terminals.