| Complementary |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| Power consumption in VA | 3.5 VA AC |
| Measurement range | 1...100 V AC/DC |
| Maximum measuring cycle | 100 ms measurement cycle as true rms value |
| Hysteresis | 3 % fixed of full scale for window mode; 5…50 % adjustable of threshold setting |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 2 % for time delay |
| Measurement error | < 1 % over the whole range with voltage variation; 0.05 %/°C with temperature variation |
| Time delay type | Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms at maximum voltage |
| Power on delay | 600 ms |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Contacts material | Cadmium free |
| Maximum power consumption in W | 1.5 W DC |
| Resistance across terminals | 110 kOhm at E2-M terminals; 22 kOhm at E1-M terminals; 220 kOhm at E3-M terminals |
| Insulation | Between supply and measurement |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60255-1 |
| Product certifications | GL; UL; CCC; EAC; CE; RCM; CSA |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz; -20…60 °C at 50 Hz |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
| Insulation resistance | > 100 MOhm at 500 V DC |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Reliability data | B10d = 290000; MTTFd = 308.2 years |
| Height | 90 mm; 88.9 mm |
| Width | 22.5 mm; 22.9 mm |
| Depth | 73 mm; 73.7 mm |
| Net weight | 0.11 kg; 0.11 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Voltage control relay |
| Product or component type | Voltage control relay |
| Relay name | RM22UA |
| Relay monitored parameters | Undervoltage and overvoltage in window mode; Overvoltage or undervoltage detection |
| Control type | With test button |
| Contacts type and composition | 2 C/O |
| Network number of phases | 1 phase |
| Supply circuit type | DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.6 cm |
| Package 1 Width | 8.2 cm |
| Package 1 Length | 9.5 cm |
| Package 1 Weight | 122.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 5.29 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 640 |
| Package 3 Height | 50.0 cm |
| Package 3 Width | 80.0 cm |
| Package 3 Length | 60.0 cm |
| Package 3 Weight | 92.58 kg |
The
voltage monitoring relay RM22UA32MR from
Schneider Electric belongs to the
Harmony control relays series and is designed for continuous monitoring of a measurement circuit for
over- or undervoltage exceeding a set voltage threshold in the range of
1 to 100 V AC/DC. The device operates as a
voltage monitor and allows selection between detecting overvoltage, undervoltage, or both in the so-called
window mode. Monitoring occurs with a measurement cycle of up to 100 ms, with the value captured as a true RMS value. The settings for the threshold, switching hysteresis, and time delay are manually adjustable via controls on the front panel. The hysteresis is fixed at 3 % of full scale in window mode, while an adjustable hysteresis of 5 to 50 % of the threshold setting is also possible. The time delay is adjustable from 0.1 to 30 seconds, with an accuracy of ±10 % of the scale value. The reset time is 1500 ms at maximum voltage, and the turn-on delay is 600 ms.
Applications include monitoring voltage supplies in industrial plants, machine controls, or in systems where stable voltage is critical for operation. The device is designed for use in single-phase systems and monitors the voltage in the measurement circuit independently of the supply voltage. Power supply is via a
wide-range power supply in the range of
24 to 240 V AC/DC, enabling universal adaptation to various supply voltages. Power consumption is 3.5 VA in AC operation and 1.5 W in DC operation. Measurement accuracy is less than 1 % across the entire range, with a temperature drift of 0.05 % per degree Celsius taken into account.
Functions and equipment in detail include two
relay changeover contacts, each rated up to 8 A. Switching capacity is 2000 VA, with a maximum switching voltage of 250 V AC. The contacts are cadmium-free and have an electrical life of 100,000 cycles and a mechanical life of 10,000,000 cycles. The output contacts are connected via screw terminals, which are designed for conductors from 0.2 to 3.3 mm² (AWG 24 to AWG 12), both solid and stranded. The terminals must be tightened with a torque of 0.6 to 1 Nm.
Technology explained simply shows that the device continuously monitors the voltage in the measurement circuit and switches the output relays when the set threshold is exceeded or undershot. Settings are adjusted via potentiometers on the front, which can be protected by a transparent cover to prevent unintended changes. An illuminated scale pointer enables visual control of the setting even from a distance. A front-mounted diagnostic switch allows temporary deactivation of the output relays to test the entire system. Closing the transparent cover automatically resets this switch. Two LEDs indicate operating and fault status.
Compatibility and accessories include use with PLC controls such as the TM221CE16T, which communicates via Ethernet and is designed for positive logic. The device is designed for industrial environments and complies with standards IEC 60255-1 and certifications GL, UL, CCC, EAC, CE, RCM, and CSA. Protection rating is IP20 at terminals, IP40 at the housing, and IP50 at the front plate, providing limited protection against touch and dust. Insulation is between supply and measurement circuit, with overvoltage category III. Operating temperature ranges from -20 to 50 °C at 60 Hz or -20 to 60 °C at 50 Hz, with storage temperature from -40 to 70 °C. Relative humidity is 93 to 97 % at 25 to 55 °C. Vibration resistance is 0.075 mm (10–58.1 Hz) and 0.035 mm (58.1–150 Hz) in operation, with shock resistance of 15 Gn (not in operation) and 5 gn (in operation). The housing is made of polycarbonate and is designed for mounting on a 35 mm DIN rail. Width is 22.5 mm, height is 90 mm.
Mounting and installation are performed on a standard 35 mm DIN rail, with screw terminals provided for wire connections. Settings are adjusted on-site, with the transparent cover protecting the controls against unintended changes. The terminals are designed for various conductor cross-sections, and tightening torques must comply with IEC 60947-1.
Operational advantages include universal voltage supply, simple adjustment of thresholds and hysteresis, high measurement accuracy, and long contact life. The integrated diagnostic function and visual LED indicators simplify maintenance and fault diagnosis. The combination of wide-range power supply and robust design makes the device suitable for a wide range of industrial applications.