| Complementary |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Supply voltage limits | 20.4…264 V AC/DC |
| Power consumption in VA | 3.5 VA AC |
| Immunity to microbreaks | 10 ms less than or equal |
| Measurement range | 0.05...5 V AC/DC |
| Maximum measuring cycle | 100 ms measurement cycle as true rms value |
| Hysteresis | 5…50 % adjustable of threshold setting |
| Setting accuracy of the switching threshold | +/- 10 % of the full scale |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit |
| Measurement error | +/- 1 %/V with voltage variation; 0.05 %/°C with temperature variation |
| Time delay type | Without |
| Reset time | 1500 ms at maximum rated voltage |
| Power on delay | 600 ms |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 12 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Utilisation category | AC-15 250 V AC 3 A conforming to IEC 60947-5-1; DC-13 24 V DC 2 A conforming to IEC 60947-5-1; AC-1 250 V AC 8 A conforming to IEC 60947-4-1; DC-1 24 V DC 5 A conforming to IEC 60947-4-1 |
| Contacts material | Cadmium free |
| Maximum power consumption in W | 1.5 W DC |
| Resistance across terminals | 5 kOhm at E1-M terminals; 30 kOhm at E2-M terminals; 50 kOhm at E3-M terminals |
| Threshold setting | 10...100 % |
| Insulation | Between supply and measurement |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60255-1 |
| Product certifications | UL; EAC; CSA; DNV; CCC; RCM; CE; UKCA |
| Marking | WEEE; China RoHS; ROHS |
| Directives | 2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz; -20…60 °C at 50 Hz; -20…50 °C; -20…60 °C |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30; 93…97 % at 25…55 °C |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 58.1…150 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 10…60.1 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 60.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50/60 Hz conforming to IEC 60255-27 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60664-1 |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1; 0.6…1.006 N.m |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) for relay ON; LED (green) for power ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Reliability data | MTTF = 308.2 years |
| Height | 90 mm; 88.9 mm |
| Width | 22.5 mm; 22.9 mm |
| Depth | 73 mm; 73.7 mm |
| Net weight | 0.11 kg; 0.11 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Product or component type | Voltage control relay |
| Relay name | RM22UA |
| Relay monitored parameters | Overvoltage detection |
| Control type | With Diagnostic button |
| Network number of phases | 1 phase |
| Supply circuit type | DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.600 cm |
| Package 1 Width | 8.200 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 120.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 5.189 kg |
Harmony Control. This voltage monitoring relay monitors a measuring circuit for exceedance of the set limit value (0.05-5 VAC/DC). Two relay changeovers are available for reporting, which can be loaded up to 8 A. The limit value and the switching hysteresis are adjustable. The settings are made using control elements on the front, which can be protected against changes under a transparent cover. An illuminated scale arrow makes it very easy to see the setting of the potentiometers, even from a distance. The diagnostic switch on the front enables the output relays to be switched off to test the entire application. When the transparent cover is closed, the diagnostic switch is automatically reset. The wide-voltage power supply (24-240 VAC/DC) enables universal use. Two LEDs show the status. The overall width is 22.5 mm and it is mounted on a top hat rail. The cable connection is made using screw terminals.