Schneider Electric RM22TU21, EAN: 3606480792168

Schneider Electric RM22TU21 voltage monitoring phase sequence/failure/undervoltage 200-240 V AC

Measurement > Other Measuring Devices

Schneider Electric RM22TU21 voltage monitoring phase sequence/failure/undervoltage 200-240 V AC

Lieske Part No. 633290
Mfg Part No RM22TU21
EAN-Code 3606480792168
Manufacturer Schneider Electric
Here only 110,20 EUR
131,14 EUR incl. VAT

Further information for Schneider Electric RM22TU21 voltage monitoring phase sequence/failure/undervoltage 200-240 V AC

Complementary
[Us] rated supply voltageself-powered
Supply voltage limits160…288 V AC
Supply frequency50...60 Hz +/- 10 %
Power consumption in VA10 VA at 240 V AC 60 Hz
Measurement range200...240 V voltage AC
Voltage detection threshold< 100 V AC
Maximum measuring cycle150 ms measurement cycle as true rms value
Threshold adjustment voltage2...20 % of Un selected
Setting accuracy of the switching threshold+/- 10 % of the full scale
Repeat accuracy+/- 0.5 % for input and measurement circuit
Measurement error< 1 % over the whole range with voltage variation; < 0.05 %/°C with temperature variation
Time delay typeWithout
Setting accuracy of time delay10 %
Reset time1500 ms at maximum voltage
Output contacts2 C/O
nominal output current8 A
Maximum switching voltage250 V AC
Switching capacity in VA2000 VA
Minimum switching current10 mA at 5 V DC
Maximum switching current8 A AC
Electrical durability100000 cycles
Mechanical durability10000000 cycles
Contacts materialCadmium free
Contractual warranty
Warranty (in months)18
Environment
StandardsIEC 60255-1
Product certificationsRCM; CE; CSA; GL; CCC; UL; EAC
Ambient air temperature for storage-40…70 °C; -40…70 °C
Ambient air temperature for operation-20…50 °C at 60 Hz; -20…60 °C at 50 Hz AC/DC
Relative humidity93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protectionIP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1; 3 conforming to UL 508
Overvoltage categoryIII conforming to IEC 60664-1; III conforming to UL 508
Dielectric test voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Insulation resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
Connections - terminalsScrew terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end
Tightening torque0.6…1 N.m conforming to IEC 60947-1
Housing materialPolycarbonate
Local signallingLED (yellow) relay ON; LED (green) power ON
Mounting support35 mm DIN rail conforming to IEC 60715
Reliability dataB10d = 350000; MTTFd = 388.1 years
Height90 mm; 88.9 mm
Width22.5 mm; 22.9 mm
Depth73 mm; 73.7 mm
Net weight0.095 kg; 0.10 kg
Logistical informations
Country of originID
Main
Range of productHarmony Control Relays
Relay typeControl relay
Product or component type3-phase control relay
Relay nameRM22TR
Relay monitored parametersUndervoltage detection; Phase sequence; Phase failure detection
Control typeWith test button
Contacts type and composition2 C/O
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.600 cm
Package 1 Width8.200 cm
Package 1 Length9.500 cm
Package 1 Weight101.000 g
Unit Type of Package 2S02
Number of Units in Package 240
Package 2 Height15 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight4.442 kg
Harmony Control. This mains monitoring relay monitors three-phase networks (200-240 VAC) for phase sequence, phase failure and undervoltage. Two relay changeovers are available for reporting, which can be loaded up to 8 A. The limit value for undervoltage (-20--2%) can be set. The settings are made using controls on the front, which can be protected against changes under a transparent cover. An illuminated scale arrow makes it very easy to see the setting of the potentiometers, even from a distance. The diagnostic switch on the front enables the output relays to be switched off to test the entire application. When the transparent cover is closed, the diagnostic switch is automatically reset. Three LEDs show the status. The width is 22.5 mm and it is mounted on a top hat rail. The cable is connected using screw terminals.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/633290
qrcode für Schneider Electric RM22TU21 voltage monitoring phase sequence/failure/undervoltage 200-240 V AC