| Complementary |
| [Us] rated supply voltage | self-powered |
| Supply voltage limits | 183…528 V AC |
| Supply frequency | 50...60 Hz +/- 10 % |
| Power consumption in VA | 15 VA at 480 V AC 60 Hz |
| Measurement range | 208...480 V voltage AC |
| Voltage detection threshold | < 100 V AC |
| Time delay type | Without |
| Reset time | 1500 ms at maximum voltage |
| Output contacts | 2 C/O |
| nominal output current | 8 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 2000 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 8 A AC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 10000000 cycles |
| Control circuit voltage limits | 183...528 V AC |
| Contacts material | Cadmium free |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60255-1 |
| Product certifications | CE; EAC; RCM; GL; CSA; UL; CCC |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C at 60 Hz; -20…60 °C at 50 Hz AC/DC |
| Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP50 (front panel) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1; 3 conforming to UL 508 |
| Overvoltage category | III conforming to IEC 60664-1; III conforming to UL 508 |
| Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |
| Insulation resistance | > 100 MOhm at 500 V DC conforming to IEC 60255-27 |
| Connections - terminals | Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (20 AWG...12 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) relay ON; LED (green) power ON |
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 924.6 years; B10d = 850000 |
| Height | 90 mm; 88.9 mm |
| Width | 22.5 mm; 22.9 mm |
| Depth | 73 mm; 73.7 mm |
| Net weight | 0.095 kg; 0.10 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Control relay |
| Product or component type | 3-phase control relay |
| Relay name | RM22TG |
| Relay monitored parameters | Phase sequence; Phase failure detection (2 or more phase cut) |
| Control type | With test button |
| Contacts type and composition | 2 C/O |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.500 cm |
| Package 1 Width | 8.200 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 104.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.616 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 640 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 86.180 kg |
Harmony Control. Dieses Netzüberwachungsrelais überwacht Drehstromnetze (208-480 VAC) auf Phasenfolge und Phasenausfall. Zur Meldung sind zwei Relaiswechsler vorhanden, die bis 8 A belastbar ist. Der frontseitige Diagnoseschalter ermöglicht das Ausschalten der Ausgangsrelais zum Test der Gesamtanwendung. Mit dem Schließen der Klarsichtabdeckung wird der Diagnoseschalter automatisch zurückgesetzt. Zwei LEDs zeigt den Status an. Die Baubreite beträgt 22,5 mm und die Montage erfolgt auf der Hutschiene. Der Leitungsanschluss erfolgt über Schraubklemmen.