| Complementary |
| [Us] rated supply voltage | self-powered |
| Supply voltage limits | 50…270 V AC/DC |
| Power consumption in VA | 0…3 VA AC |
| Measurement range | 65...260 V AC/DC |
| Maximum measuring cycle | 150 ms measurement cycle as true rms value |
| Hysteresis | 5 % fixed of threshold setting |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit; +/- 1 % for time delay |
| Time delay type | Adjustable 0.1...10 s, 0 + 10 % Tt- time delay upon fault |
| Setting accuracy of time delay | 10 % |
| Reset time | 1500 ms time delay |
| Power on delay | 1000 ms DC; 500 ms AC |
| Output contacts | 1 C/O |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC/DC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC/DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Maximum power consumption in W | 1 W DC |
| Control circuit frequency | 50...60 Hz +/- 10 % |
| Measurement accuracy | +/- 10 % of the full scale value |
| Polarity | Non reversible polarity on DC supply |
| Quality labels | CE |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-6 |
| Product certifications | UL; GL; GOST; C-Tick; CSA |
| Directives | 73/23/EEC - low voltage directive; 89/336/EEC - electromagnetic compatibility |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...2 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON; LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Reliability data | B10d = 470000; MTTFd = 502.2 years |
| Height | 90 mm; 88.9 mm |
| Width | 17.5 mm; 17.8 mm |
| Depth | 72 mm; 71.1 mm |
| Net weight | 0.09 kg; 0.09 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Voltage control relay |
| Product or component type | Voltage control relay |
| Relay name | RM17UBE |
| Relay monitored parameters | Overvoltage and undervoltage detection |
| Control type | Without test button |
| Contacts type and composition | 1 C/O |
| Product specific application | For single-phase and DC supply |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.800 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 9.700 cm |
| Package 1 Weight | 81.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.408 kg |
Harmony Control. Dieses Spannungsüberwachungsrelais überwacht einphasige Versorgungen 65-260 VAC/DC (50-60 Hz) auf Über- und Unterschreitung eines einstellbaren Grenzwertes im Fenstermodus. Zur Meldung ist ein Relaiswechsler vorhanden, der bis 5 A belastbar ist. Der untere und obere Grenzwert und eine Abschaltverzögerung sind einstellbar. Die Einstellungen erfolgen über Bedienelemente in der Front, die unter einer Klarsichtabdeckung gegen Veränderungen geschützt werden können. Zwei LEDs zeigt den Status an. Die Energieversorgung des Gerätes wird der Messspannung entnommen (Nennspannungsbereich 110-240 VAC/DC, 50-60 Hz). Die Baubreite beträgt 17,5 mm und die Montage erfolgt auf der Hutschiene.