| Additional features |
| [UH,nom] Rated operating voltage | battery operated |
| Supply voltage limits | 183…528 V AC |
| Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
| Measuring range | 220 - 480 V AC |
| Voltage detection threshold | 183 V |
| Maximum measurement cycle | 150 ms measurement cycle as true RMS value |
| Adjustable voltage for threshold | 2 - 20 % of selected Un; -2 - -17 % in range 220 V AC; +2 - +10 % in range 480 V AC; -2 - -12 % in range 208 V AC |
| Hysteresis | 2 % |
| Repeatability | ± 0.5 % for input and measurement circuit; ± 1 % for time delay |
| Time delay | Adjustable 0.3 - 30 s, 0 + 10 % Tt – delay time during fault |
| Time delay adjustment accuracy | 10 % |
| Reset time | 1500 ms reset time |
| [tA] Response time | < 200 ms (on occurrence of fault) |
| On-delay | 650 ms |
| Output contacts | 1 changeover contact |
| Rated output current | 5 A |
| Max. switching voltage | 250 V AC/DC |
| Switching power in VA | 1250 VA |
| Min. switching current | 10 mA at 5 V DC |
| Max. switching current | 5 A AC/DC |
| Electrical lifetime | 100000 cycles |
| Mechanical life | 30000000 cycles |
| Control circuit frequency | 50 - 60 Hz ± 10 % |
| Accuracy of measurement | ± 10 % of full scale value |
| Conformity marking | CE |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Harmony control relay |
| Device type | Voltage monitor |
| Product or component type | 3-phase control relay |
| Relay designation | RM17UB3 |
| Relay-monitored parameters | overvoltage and undervoltage between phases |
| Control type | Without test button |
| Contact type and composition | 1 changeover contact |
| Product-specific application | For 3-phase supply |
| Mounting |
| Electromagnetic compatibility | Emission standard for industrial environments complies with IEC 61000-6-4; Emission standard for residential, commercial and light industrial areas complies with IEC 61000-6-3; Immunity for industrial environments complies with NF EN/IEC 61000-6-2 |
| Standards | IEC 60255-1 |
| Product certifications | GOST; UL; GL; C-Tick; CSA |
| Policies | 89/336/EEC - electromagnetic compatibility; 73/23/EEC - low voltage directive |
| Ambient temperature during storage | -40…70 °C; -40…70 °C |
| Operating ambient temperature | -20…50 °C |
| Relative humidity | 95 % at 55 °C corresponds to IEC 60068-2-30 |
| Degree of protection (IP) | IP20 (terminals) in accordance with IEC 60529; IP30 (housing) in accordance with IEC 60529 |
| Pollution degree | 3 entspricht IEC 60664-1 |
| Over voltage category | III corresponds to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz |
| Insulation resistance | > 500 MOhm at 500 V DC corresponds to IEC 60255-5 |
| [Ui] Rated insulation voltage | 400 V corresponds to IEC 60664-1 |
| Operating position | Any position without power reduction |
| Connections - terminals | Screw terminals, 1 x 0.5 - 4 mm² (AWG 20 - AWG 11) solid without cable end; screw terminals, 2 x 0.5 - 2.5 mm² (AWG 20 - AWG 14) solid without cable end; screw terminals, 1 x 0.2 - 2 x 2.5 mm² (AWG 24 - AWG 12) fine-stranded with cable end; screw terminals, 2 x 0.2 - 1.5 mm² (AWG 24 - AWG 16) fine-stranded with cable end |
| [M] tightening torque | 0.6…1 Nm corresponds to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (green) for power ON; LED (yellow) for relay ON |
| Mounting bracket | 35 mm symmetrical DIN rail, conforms to IEC 60715 |
| Reliability data | B10d = 470.000; MTTFd = 502.2 years |
| Height | 90 mm; 88,9 mm |
| Width | 17,5 mm; 17,8 mm |
| Depth | 72 mm; 71,1 mm |
| Product weight | 0,08 kg; 0,08 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 2,400 cm |
| VPE 1 width | 7,800 cm |
| VPE 1 length | 9,900 cm |
| Packaging weight (Lbs) | 87,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 48 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 4,675 kg |
Harmony Control. This voltage monitoring relay monitors three-phase supplies 208-480 VAC (50-60 Hz) for phase failure, as well as exceeding or falling below an adjustable limit value. A relay changer is available for reporting, which can be loaded up to 5 A. The two limit values and a switch-off delay are adjustable. The settings are made using control elements on the front, which can be protected against changes under a transparent cover. Two LEDs show the status. The device is powered by the measuring voltage. The width is 17.5 mm and it is mounted on the top hat rail.