| Complementary |
| [Us] rated supply voltage | self-powered |
| Supply voltage limits | 183…528 V AC |
| Supply frequency | 50/60 Hz +/- 10 % |
| Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
| Measurement range | 208...480 V AC |
| Measurement voltage limits | 183…528 V AC |
| Voltage detection threshold | < 100 V AC |
| Time delay type | Without |
| Output contacts | 1 C/O |
| nominal output current | 5 A |
| Maximum switching voltage | 250 V AC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Control circuit voltage limits | - 12 % + 10 % Un |
| Control circuit frequency | 50...60 Hz +/- 10 % |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4; Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3; Immunity for industrial environments conforming to IEC 61000-6-2 |
| Standards | IEC 60255-1 |
| Product certifications | C-Tick; GL; CSA; UL; GOST |
| Marking | CE |
| Directives | 73/23/EEC - low voltage directive; 89/336/EEC - electromagnetic compatibility |
| Ambient air temperature for storage | -40…70 °C; -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529; IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end; Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end; Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Polycarbonate |
| Local signalling | LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Reliability data | MTTFd = 924.6 years; B10d = 850000 |
| Height | 90 mm; 88.9 mm |
| Width | 17.5 mm; 17.8 mm |
| Depth | 72 mm; 71.1 mm |
| Net weight | 0.085 kg; 0.09 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Control Relays |
| Relay type | Control relay |
| Product or component type | 3-phase control relay |
| Relay name | RM17TG |
| Relay monitored parameters | Phase sequence; Phase failure detection (2 or more phase cut) |
| Control type | Without test button |
| Contacts type and composition | 1 C/O |
| [Uc] control circuit voltage | 208...480 V |
| Product specific application | For 3-phase supply |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.700 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 82.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.439 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 768 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 81.828 kg |
Harmony Control. This network monitoring relay monitors three-phase networks for phase sequence and phase failure. A relay changer is available for reporting, which can be loaded up to 5 A. An LED shows the status. The width is 17.5 mm and it is mounted on the top hat rail. Supply from the measuring circuit 208-480 VAC (50-60 Hz).