| Complementary |
| Contacts material | Cadmium free |
| [Us] rated supply voltage | 24 V AC 50/60 Hz |
| Voltage range | 0.85...1.15 Us |
| [In] rated current | 5 A AC |
| Repeat accuracy | +/- 0.5 % |
| Setting accuracy of time delay | 10 % at full scale at 25 °C conforming to IEC 61812-1 |
| Temperature drift | 0.05 %/°C |
| maximum reset time | 250 ms after time delay, on de-energisation; 50 ms during time delay, on de-energisation |
| Voltage drift | +/- 0.2 %/V |
| Maximum switching capacity | 4 x 5 A |
| maximum temporary permissible current | 10 A for < 10 s |
| minimum switching current | 100 mA |
| Electrical durability | 100000 cycles at 250 V AC resistive |
| Mechanical durability | 10000000 cycles |
| maximum power consumption | 1.7 VA |
| [Ui] rated insulation voltage | 250 V conforming to IEC 255 Group C; 250 V conforming to VDE 0010 |
| Output overvoltage protection | 2 J |
| Surge withstand | 2 kV conforming to IEC 61000-4-5 level 3 |
| Creepage distance | 4 kV/3 conforming to IEC 60664-1 |
| Local signalling | 1 LED (red) for output in operation; 1 LED (yellow) for power ON |
| Function available | A- Power on-delay relay-4 C/O |
| Control type | Without test button |
| Shape of pin | Flat |
| Number of functions | 1 |
| Net weight | 0.05 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Immunity to microbreaks | 5 ms |
| Dielectric strength | 2 kV for 1 mA/1 minute at 50 Hz conforming to IEC 60601-1; 2 kV for 1 mA/1 minute at 50 Hz conforming to IEC 61812-1 |
| Standards | IEC 60601-1; 89/336/EEC; IEC 61812-1; IEC 60601-2; 73/23/EEC; 93/68/EEC; IEC 61000-6-2; EN 50081-2 |
| Product certifications | UL; cUL |
| Ambient air temperature for operation | -20…60 °C |
| Ambient air temperature for storage | -40…70 °C |
| IP degree of protection | IP50 conforming to IEC 60529 |
| Vibration resistance | 0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 95 % without condensation conforming to IEC 60068-2-6 |
| Resistance to electrostatic discharge | 6 kV in contact conforming to IEC 61000-4-2 level 3; 8 kV in air conforming to IEC 61000-4-2 level 3 |
| Resistance to electromagnetic fields | 10 V/m conforming to IEC 61000-4-3 level 3 |
| Resistance to fast transients | 2 kV conforming to IEC 61000-4-4 level 3 |
| Immunity to radioelectric fields | 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 level 3 |
| Immunity to voltage dips | >= 95 % / 1 s conforming to IEC 61000-4-11; 30 % / 10 ms conforming to IEC 61000-4-11; 60 % / 100 ms conforming to IEC 61000-4-11 |
| Disturbance radiated/conducted | Class B conforming to EN 55022 (EN 55011 group 1) |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range of product | Harmony Timer Relays |
| Fixing mode | Plug-in (socket) |
| Product or component type | Miniature timing relay |
| Discrete output type | Relay |
| Contacts type and composition | 4 C/O |
| Component name | REXL |
| Time delay type | Power on-delay |
| Time delay range | 6...60 s; 1...10 s; 1...10 h; 1...10 min; 6...60 min; 10...100 h; 0.1...1 s |
| Width | 21 mm |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.500 cm |
| Package 1 Width | 3.000 cm |
| Package 1 Length | 3.000 cm |
| Package 1 Weight | 49.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 2.666 kg |
Harmony Time. This time relay design is specially designed to be operated in classic plug-in sockets of industrial plug-in relays. The time relay is simply plugged into the assembled and wired socket. This means that a quick change can be made in the event of maintenance without having to loosen the cable connections. The time range can be easily set using the ring on the front and 2 LEDs show the status. Time function with response delay - time range 0.1 s - 100 h - outputs 4 relay changers, each with a load of up to 5 A - supply voltage 24 VAC (50/60 Hz).