| Complementary |
| Product compatibility | Wireless access point |
| Maximum power consumption in W | 3.5 W 110...277 V |
| Maximum power consumption in VA | 12 VA at 110...277 V |
| Communication network type | Ethernet 10/100BASE-T; Wi-Fi infrastructure2.4 GHz; Wi-Fi infrastructure5 GHz; Wi-Fi access point2.4 GHz; Wireless IEEE 802.15.4 |
| Communication port protocol | Modbus TCP; DHCP; HTTPS; NTP/SNTP; IPv4; IPv6; TCP/IP |
| Communication port support | 1 RJ45: ETHERNET |
| Number of server device(s) | 20 wireless (IEEE 802.15.4) product(s) - mixed |
| Number of devices | 64 Modbus TCP/IP |
| Memory capacity | 512 MB NAND |
| Number of inputs | 0 |
| Connections - terminals | Power supply: screw terminal block (top) 1.5…2.5 mm² cable(s) ; Communication: screw terminal block (bottom) 0.14…1.5 mm² cable(s) |
| Tightening torque | Power supply: 0.6 N.m; Communication: 0.25 N.m |
| Wire stripping length | Power supply: 7 mm; Communication: 7 mm |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Product certifications | CE; cULus; CB; RCM; UKCA; FCC; IC; DNV Marine; ANSI RF; IACS E10 |
| Standards | IEC 61010; IEC 61010-1; IEC 61010-2-201; UL 61010; UL 61010-1; UL 61010-2-201; EN 61010-1; EN 61010-2-201; CAN/CSA C22.2 No. 61010-1-12; CAN/CSA C22.2 No. 61010-2-201; IEC 62974-1; IEC 61326-1; EN 61326-1; ETSI EN 301 489-1; ETSI EN 301 489-17; EN 301-893; EN 55032; CISPR 11; ETSI EN 300 328; IEEE 802.15.4; IEEE 802.11a/b/g/n; IEEE 802.3 af/at; FCC CFR 47 part 15 class A; EN 62311; IEC 62311; ANSI C63.10; EN 62974-1; DNVGL-GC-0339 |
| Depth | 70.2 mm |
| Height | 93 mm |
| Width | 54 mm |
| Net weight | 163 g |
| Data recording | Real time data monitoring |
| Data buffer for data publication (cloud, SFTP, HTTPS) depending on network | 1 month(s) |
| Function available | Embedded web page for configuration and upgrade; Diagnosis capabilities; Diagnostic report; Diagnostics on communication; Energy management; With integrated web server; Firmware update; Backup/restore configuration; Configurable event |
| Product specific application | Wireless Schneider Electric devices ecosystem |
| Web services | HTTPS server; SFTP publication (CSV / JSON); HTTPS publication (CSV / JSON) |
| Communication service | Device Profile for Web Services (DPWS); Modbus TCP server; SNTP client; DHCP client; RSTP |
| Commissioning interface | EcoStruxure Power Commission desktop; EcoStruxure Power Commission Mobile (through Wi-Fi Access point); Web page |
| Realtime clock | With RTC-battery set; With user calibration |
| Time synchronisation protocol | NTP; SNTP |
| Range compatibility | EcoStruxure Facility Expert; EcoStruxure Building Operation; EcoStruxure Power Operation; EcoStruxure Power Monitoring Expert; EcoStruxure Asset Advisor; EcoStruxure Energy Hub; EcoStruxure Resource Advisor; Third party SCADA |
| Communication iinterface | Wireless (IEEE802.15.4) product |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Relative humidity | 5…95 % |
| IP degree of protection | IP40 (front face); IP20 (casing) |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Pollution degree | 2 |
| Operating altitude | < 2000 m |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | EcoStruxure |
| Product name | Panel Server Entry |
| Product or component type | Gateway |
| Device short name | PAS400 |
| Device application | Gateway |
| [Us] rated supply voltage | 110...277 V AC 50/60 Hz |
| Communication gateway | Ethernet TCP/IP to wireless devices |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 8.500 cm |
| Package 1 Length | 10.500 cm |
| Package 1 Weight | 206.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 45 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 10.300 kg |
The EcoStruxure Panel Server Entry is an Ethernet (Modbus TCP) connection gateway for up to 20 end devices (e.g. PowerTag) that communicate wirelessly via radio, with web pages for data display. For connected PowerTags, it offers alarm management via email for final circuits as well as accurate real-time measurements of energy, power, current and voltage. Easy commissioning through integrated web server or with EcoStruxure Power Commission for configuration report and register documentation. Easy troubleshooting in the system through extended diagnostic information and event logs. Data buffer of selected measured values for approx. 1 month for Schneider Electric cloud applications. One 10/100 Base-T Ethernet RJ45 connection. Important certifications such as CE, UL/CSA, IEC61010, UL61010, IEC61974-1, Marine Certification, IEC61443-4-2, RCM, EAC and UKCA. Power supply from 110 to 277 VAC/DC 50-60Hz 3W/10VA max. Mounting on DIN rail, 3 modules, width 54 mm, depth 70.2 mm and height 85 mm. Operating temperature -25°C to +60°C and relative humidity -5-95%.