Further information for Schneider Electric NHJF36150TW motor protection switch 150A 3P
Additional features
Pole description
3P
Control type
Toggle switch
Mounting mode
Device holder
Mounting bracket
Installation; DIN rail; rear panel
Electrical connection
Connection nut, line side; connection nut, load side
[In] Rated current
150 A at 40 °C
[Ui] Rated insulation voltage
750 V AC 50/60 Hz corresponds to IEC 60947-2
[Uimp] Rated impulse voltage withstand
8 kV corresponds to IEC 60947-2
[Ue] Rated operational voltage
525 V AC 50/60 Hz complies with IEC 60947-2; 690 V AC 50/60 Hz complies with IEC 947-2; 600 V AC 50/60 Hz complies with UL 489
Breaking capacity
HJ
Application category
Category A
Mechanical life
4000 cycles
Electrical lifetime
4000 cycles
Terminal pitch
45 mm
Local signalling
ON/OFF indicator
Trigger name
TM
Trigger technology
Thermal-magnetic
Tripping unit protection functions
Basic protection
Trigger power
150 A
Display type
3 LEDs
Rated switching-off capacity Ics
Ics: 100 kA at 220/240 V - AC according to IEC 947-2; Ics: 65 kA at 380/415 V - AC according to IEC 947-2; Ics: 65 kA at 440/480 V - AC according to IEC 947-2; Ics: 25 kA at 500/525 V - AC according to IEC 947-2
[Ir] type of long-time pickup setting
Fixed
Adjustment range for long exposure
1 In
[Isd] Type of short-time pick-up adjustment
Fixed
[Isd] Short-time pick-up adjustment range
1700 A
Over voltage category
II
Provisions for padlocks
Not lockable
Height
163 mm
Width
104 mm
Depth
86 mm
Standards
W-C-375B/GEN; UL 489; IEC 60947-2; NMX J-266; CSA C22.2 No. 5; NEMA AB1
Product certifications
CCC; CE
Product weight
2,2 kg
Tightening moment
5 Nm for 2.5…95 mm² (AWG 14 - AWG 3/0)
Suitability for insulation
Contact position indicator
Contractual warranty
Warranty (in months)
18
Main features
Product series
PowerPact Multistandard
Product name
H-Frame
Device short name
H-frame
Product or component type
Power-cut-out switch
Device application
Distribution
Mounting
Degree of protection (IP)
IP40 complies with IEC 60529
Degree of protection (IK)
IK07 corresponds to IEC 62262
Pollution degree
3 corresponds to IEC 60947-1; 3 corresponds to IEC 60664-1