| Additional features |
| Power quality analysis | up to the 63rd harmonic; differential current monitoring |
| Instrument type | Measured neutral conductor current; Calculated earth fault current; Fault current I0 |
| Device application | Gateway; collection of S0 pulses for measurement of water, air, gas, electricity, steam; current monitoring; multi-tariff |
| Measured value type | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| Supply voltage | 100 - 300 V DC; 90 - 528 V AC 45 - 65 Hz |
| Network frequency | 60 Hz; 50 Hz |
| [In] Rated current | 1 A; 5 A |
| Type of network | 3P + N; 3P; 1P + N |
| Maximum power consumption in VA | 16 VA at 480 V |
| Throughput time | 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical |
| Display type | Integrated monochrome graphic LCD display |
| Display resolution | 128 x 128 pixels |
| Scanning interval | 128 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance |
| Measuring voltage | 20…400 V AC 45 - 65 Hz between phase and neutral; 20…828 V AC 45 - 65 Hz between phases |
| Measuring range for frequency | 45…65 Hz |
| Number of inputs | 4 digital |
| Accuracy of measurement | Apparent power ± 0.5 %; frequency ± 0.05 %; active energy ± 0.2 %; reactive energy ± 1 %; active power ± 0.2 %; voltage ± 0.1 %; power factor ± 0.005; current ± 0.15 % |
| Accuracy class | Class 0,2S active energy according to IEC 62053-22 |
| Number of outputs | 2 digital |
| Displayed information | Tariff (8) |
| Communications protocol | Modbus RTU and ASCII at 9, 6, 19, 2 and 38.4 kBaud even/odd or none - 2-wire, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP; DNP3 over Ethernet |
| Support for communication interfaces | RS485; Ethernet |
| Communication gateway | Ethernet/serial |
| Data logging | Event logging; Maintenance logs; Minimum/maximum values of real-time values; Data logs; Alarm logs; Timestamping |
| Memory capacity | 1,1 MB |
| Web services | Alarm notification via email; web server; diagnostics via predefined web pages; real-time data display |
| Ethernet Service | SNTP client; SNMP messages |
| Connections - terminals | Voltage circuit: screw terminal block 4; control circuit: screw terminal block 2; current transformer: screw terminal block 6; RS485 connection: screw terminal block 4; digital input: screw terminal block 8; digital output: screw terminal block 4; Ethernet network: RJ45 connector 2 |
| Mounting mode | Flush-mounted |
| Mounting bracket | Frame conditions |
| Standards | EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE compliant with IEC 61010-1; CULus compliant with UL 61010-1; MID compliant with EN 50470-1; MID compliant with EN 50470-3 |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Product weight | 450 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5661 |
| Mounting |
| Degree of protection (IP) | IP54 display: complies with IEC 60529; IP30 rear side: complies with IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -40…85 °C |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 12,5 cm |
| VPE 1 width | 12,5 cm |
| VPE 1 length | 11,5 cm |
| Packaging weight (Lbs) | 605,0 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 12 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 7,883 kg |