| Complementary |
| Power quality analysis | up to the 63rd harmonic |
| Metering type | Measured neutral current; Calculated ground current |
| Device application | Gateway; WAGES metering; Power monitoring; Multi-tariff |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 24 V DC |
| Network frequency | 60 Hz; 50 Hz |
| [In] rated current | 1 A; 5 A |
| type of network | 3P + N; 3P; 1P + N |
| Maximum power consumption in VA | 16 VA at 480 V |
| Ride-through time | 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical |
| Display type | Monochrome graphic LCD |
| Display resolution | 128 x 128 pixels |
| Sampling rate | 128 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance |
| Measurement voltage | 20…400 V AC 45...65 Hz between phase and neutral; 20…828 V AC 45...65 Hz between phases |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 4 digital |
| Measurement accuracy | Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Active energy +/- 0.2 %; Reactive energy +/- 1 %; Active power +/- 0.2 %; Voltage +/- 0.1 %; Power factor +/- 0.005; Current +/- 0.15 %; Reactive power +/- 1 % |
| Accuracy class | Class 0.2S active energy conforming to IEC 62053-22 |
| Number of outputs | 2 digital |
| Information displayed | Tariff (8) |
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP; DNP3 over ethernet |
| Communication port support | RS485; ETHERNET |
| Communication gateway | Ethernet/serial |
| Data recording | Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping |
| Memory capacity | 1.1 MB |
| Web services | Alarm notification by e-mail; Web server; Diagnostic via predefined web pages; Real time viewing of data |
| Ethernet service | SNTP client; SNMP-Traps |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; RS485 link: screw terminal block4; Digital input: screw terminal block8; Digital output: screw terminal block4; Ethernet network: RJ45 connector2 |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Standards | EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1 |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 450 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5580 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.500 cm |
| Package 1 Width | 12.500 cm |
| Package 1 Length | 13.000 cm |
| Package 1 Weight | 575.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.440 kg |
The PowerLogic PM5580 is a universal meter for front mounting (96 mm x 96 mm) with a fully graphic and backlit LCD display. The meter offers an accuracy of class 0.2s according to the IEC 62053-22 standard and 128 samples per cycle. The meter measures energy, active and reactive power, voltage, current, frequency, power factor and up to the 63rd harmonic. With 4 quadrant energy measurement. 1.1 MegaBytes memory for up to 14 selectable parameters with configurable interval and duration. This meter also has direct neutral monitoring. The device operates in a DC network and accepts a supply voltage of 24 VDC. The rated current of this meter is 1 A or 5 A and supports configurations with one phase and neutral, three phases or three phases and neutral. The measuring voltage range between phases is 20 to 690 VAC at 45 to 65 Hz. The measuring range between phase and neutral is 20 to 400 VAC at 45 to 65 Hz. Communication protocols are Modbus RTU and ASCII 2 wires with RS485 interface as well as Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, Daisy Chain Ethernet with RJ45 connection support. The integrated communication functions enable support of the DNP 3.0 protocol, access to an integrated web server and a serial to Ethernet gateway. The meter also has 4 digital inputs with pulse support and 2 digital outputs. There are 52 configurable alarms and 8 tariffs are supported. The product dimensions are as follows: width 96 millimeters, depth 77 millimeters, height 96 millimeters and product weight 450 g.