| Complementary |
| Power quality analysis | up to the 63rd harmonic |
| Metering type | Measured neutral current; Calculated ground current |
| Device application | Power monitoring; WAGES metering; Gateway; Multi-tariff |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 100...300 V DC; 90...528 V AC 45...65 Hz |
| Network frequency | 60 Hz; 50 Hz |
| [In] rated current | 5 A; 1 A |
| type of network | 1P + N; 3P; 3P + N |
| Maximum power consumption in VA | 16 VA at 480 V |
| Ride-through time | 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical |
| Display type | Without display |
| Sampling rate | 128 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance |
| Measurement voltage | 20…400 V AC 45...65 Hz between phase and neutral; 20…828 V AC 45...65 Hz between phases |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 4 digital |
| Measurement accuracy | Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Active energy +/- 0.2 %; Reactive energy +/- 1 %; Active power +/- 0.2 %; Voltage +/- 0.1 %; Power factor +/- 0.005; Current +/- 0.15 %; Reactive power +/- 1 % |
| Accuracy class | Class 0.2S active energy conforming to IEC 62053-22 |
| Number of outputs | 2 digital |
| Information displayed | Tariff (8) |
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP; DNP3 over ethernet |
| Communication port support | RS485; ETHERNET |
| Communication gateway | Ethernet/serial |
| Data recording | Maintenance logs; Event logs; Alarm logs; Time stamping; Data logs; Min/max of instantaneous values |
| Memory capacity | 1.1 MB |
| Web services | Alarm notification by e-mail; Diagnostic via predefined web pages; Web server; Real time viewing of data |
| Ethernet service | SNMP-Traps; SNTP client |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; RS485 link: screw terminal block4; Digital input: screw terminal block8; Digital output: screw terminal block4; Ethernet network: RJ45 connector2 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Standards | EN 50470-1; IEC 60529; IEC 62053-24; UL 61010-1; IEC 62053-22:2020; IEC 61557-12:2015; EN 50470-3; ANSI C12.20; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; BTL |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 450 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5563 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.000 cm |
| Package 1 Width | 12.600 cm |
| Package 1 Length | 12.600 cm |
| Package 1 Weight | 547.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.150 kg |
Das PowerLogic PM5563 ist ein Universalmessgerät für die DIN-Schiene ohne Display. Das Messgerät bietet eine Genauigkeit der Klasse 0,2s gemäß der Norm IEC 62053-22 und 128 Abtastungen pro Zyklus. Das Messgerät misst Energie, Wirk- und Blindleistung, Spannung, Strom, Frequenz, Leistungsfaktor und bis zur 63. Oberschwingung. Mit 4 Quadranten Energiemessung. 1,1 MegaBytes Speicher für bis zu 14 wählbare Parameter mit konfigurierbarem Intervall und Dauer. Dieses Messgerät verfügt auch über eine direkte Überwachung des Neutralleiters. Das Gerät funktioniert in einem 50Hz oder 60Hz Netz und akzeptiert eine Versorgungsspannung von 100 bis 480 VAC und 125 bis 250 VDC. Der Bemessungsstrom dieses Messgerätes beträgt 1 A oder 5 A und unterstützt Konfigurationen mit einer Phase und Neutralleiter, drei Phasen oder drei Phasen und Neutralleiter. Der Bereich der Messspannung zwischen den Phasen beträgt 20 bis 690 VAC bei 45 bis 65 Hz. Der Messbereich zwischen Phase und Nullleiter beträgt 20 bis 400 VAC bei 45 bis 65 Hz. Kommunikationsprotokolle sind Modbus RTU und ASCII 2 Drähte mit Schnittstelle RS485 sowie Modbus TCP/IP, Ethernet/IP und BACnet/IP basierend auf 10/100 Mbit/s, Daisy Chain Ethernet mit RJ45 Anschlussunterstützung. Die integrierten Kommunikationsfunktionen ermöglichen die Unterstützung des DNP 3.0 Protokolls, den Zugriff auf einen integrierten Webserver und ein serielles zu Ethernet Gateway. Das Messgerät verfügt auch über 4 digitale Eingänge mit Impuls Unterstützung und 2 digitale Ausgänge. Es gibt 52 konfigurierbare Alarme und es werden 8 Tarife unterstützt. Die Produktabmessungen sind wie folgt: Breite 96 Millimeter, Tiefe 77 Millimeter, Höhe 96 Millimeter und Produktgewicht 450 g.