| Complementary |
| Power quality analysis | up to the 63rd harmonic |
| Metering type | Measured neutral current; Calculated ground current |
| Device application | Gateway; WAGES metering; Power monitoring; Multi-tariff |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 100...300 V DC; 90...528 V AC 45...65 Hz |
| Network frequency | 60 Hz; 50 Hz |
| [In] rated current | 1 A; 5 A |
| type of network | 3P + N; 3P; 1P + N |
| Maximum power consumption in VA | 16 VA at 480 V |
| Ride-through time | 35 ms 120 V AC typical; 129 ms 230 V AC typical; 50 ms 125 V DC typical |
| Display type | Backlit LCD |
| Display resolution | 128 x 128 pixels |
| Sampling rate | 128 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance |
| Measurement voltage | 20…400 V AC 45...65 Hz between phase and neutral; 20…828 V AC 45...65 Hz between phases |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 4 digital |
| Measurement accuracy | Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Active energy +/- 0.2 %; Reactive energy +/- 1 %; Active power +/- 0.2 %; Voltage +/- 0.1 %; Power factor +/- 0.005; Current +/- 0.15 %; Reactive power +/- 1 % |
| Accuracy class | Class 0.2S active energy conforming to IEC 62053-22 |
| Number of outputs | 2 digital |
| Information displayed | Tariff (8) |
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS; Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; Ethernet Modbus TCP/IP daisy chain; BACnet IP; DNP3 over ethernet |
| Communication port support | RS485; ETHERNET |
| Communication gateway | Ethernet/serial |
| Data recording | Event logs; Maintenance logs; Min/max of instantaneous values; Data logs; Alarm logs; Time stamping |
| Memory capacity | 1.1 MB |
| Web services | Alarm notification by e-mail; Diagnostic via predefined web pages; Web server; Real time viewing of data |
| Ethernet service | SNTP client; SNMP-Traps |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; RS485 link: screw terminal block4; Digital input: screw terminal block8; Digital output: screw terminal block4; Ethernet network: RJ45 connector2 |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Standards | EN 50470-3; IEC 61557-12:2015; IEC 62053-22:2020; IEC 62053-24; IEC 60529; EN 50470-1; UL 61010-1; ANSI C12.20; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; BTL |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 450 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5560 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.000 cm |
| Package 1 Width | 12.600 cm |
| Package 1 Length | 12.600 cm |
| Package 1 Weight | 598.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.900 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 96 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 77.372 kg |
The PowerLogic PM5560 from Schneider Electric is a
power meter for front mounting in enclosures, designed for
energy and power monitoring in industrial and commercial installations. The device features a
fully graphical, backlit LCD display with a resolution of 128 x 128 pixels, enabling clear presentation of measurement values and status information. It is designed for use in networks with 50 Hz or 60 Hz and supports various network types, including 3P + N, 3P, and 1P + N. The supply voltage ranges from 100 to 300 V DC and 90 to 528 V AC, with a maximum power consumption of 16 VA at 480 V. The rated currents are 1 A and 5 A, and the device measures in the current range of 50 to 10000 mA. The measurement voltage is between phase and neutral conductor 20 to 400 V AC and between phases 20 to 828 V AC, each within a frequency range of 45 to 65 Hz.
Applications include monitoring energy consumption, power quality, and network parameters in industrial installations, building technology, and energy distribution systems. The device measures
active and reactive power, voltage, current, frequency, power factor, energy, as well as
harmonics up to the 63rd harmonic. Measurement accuracy is ± 0.2 % for active energy, ± 1 % for reactive energy, ± 0.2 % for active power, ± 0.1 % for voltage, ± 0.15 % for current, and ± 0.05 % for frequency. Accuracy class 0.2S corresponds to standard IEC 62053-22. The sampling rate is 128 samples per cycle, enabling precise capture of load profiles. The device also monitors
neutral conductor current and calculates
earth fault current, which is important for diagnosing insulation faults and network disturbances.
Functions and equipment in detail include 4 digital inputs capable of capturing S0 pulses for measurements of water, air, gas, electricity, and steam, as well as 2 digital outputs for alarm signals or control functions. It supports up to 8 tariffs and offers 52 configurable alarms. Data logging includes event logs, maintenance logs, minimum and maximum values of real-time values, data logs, and alarm logs with timestamping. The storage capacity is 1.1 MB, allowing long-term recording of up to 14 selectable parameters with configurable intervals and duration.
Technology explained simply shows that the device features an integrated communication platform. It supports
Modbus RTU and ASCII over RS485 (2-wire, isolated 2500 V),
Modbus TCP/IP over Ethernet (10/100 Mbit/s, isolated 2500 V),
BACnet IP, and
DNP3 over Ethernet. An integrated web server enables diagnostics via predefined web pages and real-time display of data. Alarm notifications via email are also possible. The device functions as a
communication gateway between serial and Ethernet networks and supports Daisy-Chain connections via RJ45 connectors. Ethernet service functions include SNTP client and SNMP messages.
Compatibility and accessories include a variety of current transformers designed for different rated currents and mounting types, such as transformers for 200/5A, 100/5A, 40/5A, 2500/5A, 1250/5A, 600/5A, 800/5A, 400/5A, 300/5A, 250/5A, 75/5A, 50/5A, and 400/5A, each with various cable or busbar connections. These transformers enable adaptation of the measuring device to different load currents and installation situations. Other compatible devices include models METSEPM5563 and METSEPM5561, which offer similar functions.
Mounting and installation are flush in enclosures using a mounting bracket for frame conditions. Dimensions are 96 mm (width) x 96 mm (height) x 72 mm (depth). The protection rating is IP54 at the display (corresponds to IEC 60529) and IP30 at the rear. The operating ambient temperature ranges from -25 °C to 70 °C, and storage temperature from -40 °C to 85 °C. Relative humidity is 5 to 95 % at 50 °C, non-condensing. The pollution degree class is 2.
Operational advantages lie in high measurement accuracy, comprehensive data processing, and versatile communication options. The integrated web server function and support for multiple protocols facilitate integration into existing building and energy management systems. Direct monitoring of the neutral conductor and harmonic capture support network quality assurance. The large storage capacity and configurable alarms enable detailed analysis of load profiles and disturbances. The device is designed for use in industrial environments with high requirements for reliability and accuracy.