| Complementary |
| Power quality analysis | up to the 31st harmonic |
| Device application | Power monitoring; Multi-tariff |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 90...450 V AC 45...65 Hz; 100...300 V DC |
| Network frequency | 50 Hz; 60 Hz |
| [In] rated current | 5 A; 1 A |
| type of network | 1P + N; 3P + N; 3P |
| Maximum power consumption in VA | 11 VA at 415 V |
| Ride-through time | 80 ms 120 V AC typical; 100 ms 230 V AC typical; 100 ms 415 V AC typical; 50 ms 125 V DC typical |
| Display type | Monochrome graphic LCD |
| Display resolution | 128 x 128 pixels |
| Sampling rate | 64 samples/cycle |
| Measurement current | 5…8500 mA |
| Analogue input type | Voltage (impedance 10 MOhm); Current (impedance |
| Measurement voltage | 35…760 V AC 45...65 Hz between phases; 20…400 V AC 45...65 Hz between phase and neutral |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 2 digital |
| Measurement accuracy | Active energy +/- 0.5 %; Reactive energy +/- 2 %; Active power +/- 0.5 %; Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Power factor +/- 0.5; Current +/- 0.5 %; Voltage +/- 0.5 %; Apparent energy +/- 0.5 %; Reactive power +/- 2 % |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
| Number of outputs | 2 relay; 2 digital |
| Information displayed | Tariff (4) |
| Communication port protocol | Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; BACnet IP |
| Communication port support | ETHERNET |
| Data recording | Alarm logs; Time stamping; Min/max of instantaneous values; Event logs; Maintenance logs; Data logs |
| Memory capacity | 256 kB |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; Input/output circuit: screw terminal block6; Relay output: screw terminal block4; Ethernet network: RJ45 connector |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Standards | IEC 60529; UL 61010-1; IEC 61557-12:2015; IEC 62053-24; IEC 62053-22:2020; EN 50470-3; EN 50470-1; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1; MID conforming to EN 50470-1; MID conforming to EN 50470-3 |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 430 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Limits for harmonic current emissions class A conforming to IEC 61000-3-2; Electrostatic discharge level 4 conforming to IEC 61000-4-2; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency level 4 conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022 |
| IP degree of protection | IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C meter; -20…70 °C display; -25…-20 °C (with reduced performance) display |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 2000 m CAT III; 3000 m CAT II |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5341 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.000 cm |
| Package 1 Width | 11.500 cm |
| Package 1 Length | 12.600 cm |
| Package 1 Weight | 503.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.648 kg |
The PowerLogic PM5341 is a universal meter for front mounting (96 mm x 96 mm) with a fully graphic and backlit LCD display and has an additional MID certification. The meter offers an accuracy of class 0.5s according to the IEC 62053-22 standard and 64 samples per cycle. The meter measures energy, active and reactive power, voltage, current, frequency, power factor and up to the 31st harmonic. With 4 quadrant energy measurement. 256 kilobytes of memory for two fixed parameters, active and reactive energy, included. The device works in a 50 Hz or 60 Hz network and accepts a supply voltage of 100 to 415 VAC and 125 to 250 VDC. The rated current of this meter is 1 A or 5 A and supports configurations with one phase and neutral, three phases or three phases and neutral. The measuring voltage range between phases is 35 to 690 VAC at 47 to 63 Hz. The measuring range between phase and neutral is 20 to 400 VAC at 45 to 65 Hz. The communication protocol is Modbus TCP/IP and BACnet/IP based on 10/100 Mbit/s, Ethernet with RJ45 connector support. The meter also has 2 configurable digital inputs or digital outputs and two relay outputs. There are 35 configurable alarms and four tariffs are supported. The product dimensions are as follows: width 96 millimeters, depth 72 millimeters, height 96 millimeters and product weight 430 g.