| Complementary |
| Power quality analysis | up to the 31st harmonic |
| Device application | Multi-tariff; Power monitoring |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 90...450 V AC 45...65 Hz; 100...300 V DC |
| Network frequency | 60 Hz; 50 Hz |
| [In] rated current | 5 A; 1 A |
| type of network | 3P; 1P + N; 3P + N |
| Maximum power consumption in VA | 11 VA at 415 V |
| Ride-through time | 100 ms 120 V AC typical; 400 ms 230 V AC typical; 50 ms 125 V DC typical |
| Display type | Monochrome graphic LCD |
| Display resolution | 128 x 128 pixels |
| Sampling rate | 64 samples/cycle |
| Measurement current | 5…9000 mA |
| Analogue input type | Voltage (impedance 10 MOhm); Current (impedance |
| Measurement voltage | 35…760 V AC 45...65 Hz between phases; 20…400 V AC 45...65 Hz between phase and neutral |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 2 digital |
| Measurement accuracy | Active energy +/- 0.5 %; Reactive energy +/- 2 %; Active power +/- 0.5 %; Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Power factor +/- 0.5; Current +/- 0.5 %; Voltage +/- 0.5 %; Apparent energy +/- 0.5 %; Reactive power +/- 2 % |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
| Number of outputs | 2 relay; 2 digital |
| Information displayed | Tariff (4) |
| Communication port protocol | Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V; BACnet IP |
| Communication port support | ETHERNET |
| Data recording | Data logs; Alarm logs; Time stamping; Event logs; Min/max of instantaneous values; Maintenance logs |
| Memory capacity | 256 kB |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; Input/output circuit: screw terminal block6; Relay output: screw terminal block4; Ethernet network: RJ45 connector |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Standards | EN 50470-1; IEC 62053-24; IEC 60529; UL 61010-1; IEC 62053-22:2020; EN 50470-3; IEC 61557-12:2015; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1 |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 430 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electromagnetic compatibility | Limits for harmonic current emissions class A conforming to IEC 61000-3-2; Electrostatic discharge level 4 conforming to IEC 61000-4-2; Conducted RF disturbances level 3 conforming to IEC 61000-4-6; Magnetic field at power frequency level 4 conforming to IEC 61000-4-8; Conducted and radiated emissions class B conforming to EN 55022 |
| IP degree of protection | IP51 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C meter; -20…70 °C display; -25…-20 °C (with reduced performance) display |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5340 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.500 cm |
| Package 1 Width | 12.700 cm |
| Package 1 Length | 12.700 cm |
| Package 1 Weight | 502.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.600 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 96 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 62.800 kg |
Das PowerLogic PM5340 ist ein Universalmessgerät für den Fronteinbau (96 mm x 96 mm) mit vollgraphischer und hinterleuchteter LCD Anzeige. Das Messgerät bietet eine Genauigkeit der Klasse 0,5s gemäß der Norm IEC 62053-22 und 64 Abtastungen pro Zyklus. Das Messgerät misst Energie, Wirk- und Blindleistung, Spannung, Strom, Frequenz, Leistungsfaktor und bis zur 31. Oberschwingung. Mit 4 Quadranten Energiemessung. 256 KiloByte Speicher für zwei feste Parameter, Wirk- und Blindenergie, enthalten. Das Gerät funktioniert in einem 50Hz oder 60Hz Netz und akzeptiert eine Versorgungsspannung von 100 bis 415 VAC und 125 bis 250 VDC. Der Bemessungsstrom dieses Messgerätes beträgt 1 A oder 5 A und unterstützt Konfigurationen mit einer Phase und Neutralleiter, drei Phasen oder drei Phasen und Neutralleiter. Der Bereich der Messspannung zwischen den Phasen beträgt 35 bis 690 VAC bei 47 bis 63 Hz. Der Messbereich zwischen Phase und Nullleiter beträgt 20 bis 400 VAC bei 45 bis 65 Hz. Das Kommunikationsprotokoll ist Modbus TCP/IP und BACnet/IP basierend auf 10/100 Mbit/s, Ethernet mit Anschluss RJ45 Unterstützung. Das Messgerät verfügt außerdem über 2 konfigurierbare digitale Eingänge oder digitale Ausgänge und zwei Relaisausgänge. Es gibt 35 konfigurierbare Alarme und es werden vier Tarife unterstützt. Die Produktabmessungen sind wie folgt: Breite 96 Millimeter, Tiefe 72 Millimeter, Höhe 96 Millimeter und Produktgewicht 430 g.