| Complementary |
| Power quality analysis | up to the 15th harmonic |
| Device application | Power monitoring |
| Type of measurement | Current; Voltage; Frequency; Power factor; Energy; Active and reactive power |
| [Us] rated supply voltage | 90...450 V AC 45...65 Hz; 100...300 V DC |
| Network frequency | 50 Hz; 60 Hz |
| [In] rated current | 1 A; 5 A |
| type of network | 1P + N; 3P + N; 3P |
| Maximum power consumption in VA | 11 VA at 415 V |
| Ride-through time | 80 ms 120 V AC typical; 100 ms 230 V AC typical; 100 ms 415 V AC typical; 50 ms 125 V DC typical |
| Display type | Monochrome graphic LCD |
| Display resolution | 128 x 128 pixels |
| Sampling rate | 64 samples/cycle |
| Measurement current | 50…8500 mA |
| Analogue input type | Voltage (impedance 5 MOhm); Current (impedance |
| Measurement voltage | 35…760 V AC 45...65 Hz between phases; 20…440 V AC 45...65 Hz between phase and neutral |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 0 |
| Measurement accuracy | Active energy +/- 0.5 %; Reactive energy +/- 2 %; Active power +/- 0.5 %; Apparent power +/- 0.5 %; Frequency +/- 0.05 %; Power factor +/- 0.5; Current +/- 0.5 %; Voltage +/- 0.5 %; Apparent energy +/- 0.5 %; Reactive power +/- 2 % |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
| Number of outputs | 1 digital |
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V; JBUS |
| Communication port support | RS485 |
| Data recording | Time stamping; Min/max of instantaneous values |
| Connections - terminals | Voltage circuit: screw terminal block4; Control circuit: screw terminal block2; Current transformer: screw terminal block6; Input/output circuit: screw terminal block6; RS485 link: screw terminal block4 |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Standards | UL 61010-1; EN 50470-3; EN 50470-1; IEC 62053-22:2020; IEC 60529; IEC 62053-24; IEC 61557-12:2015; IEC 62053-23:2020; IEC 62052-11:2020; IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1; CULus conforming to UL 61010-1 |
| Width | 96 mm |
| Depth | 72 mm |
| Height | 96 mm |
| Net weight | 380 g |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP54 display: conforming to IEC 60529; IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % at 50 °C non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25…70 °C meter; -20…70 °C display; -25…-20 °C (with reduced performance) display |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 2000 m CAT III |
| Logistical informations |
| Country of origin | IN |
| Main |
| Range | PowerLogic |
| Product name | PowerLogic PM5000 |
| Product or component type | Power meter |
| Device short name | PM5110 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.000 cm |
| Package 1 Width | 12.600 cm |
| Package 1 Length | 12.600 cm |
| Package 1 Weight | 478.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.345 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 96 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 61.820 kg |
Das PowerLogic PM5110 ist ein Universalmessgerät für den Fronteinbau (96 mm x 96 mm) mit vollgraphischer und hinterleuchteter LCDAnzeige. Das Messgerät bietet eine Genauigkeit der Klasse 0,5s gemäß der Norm IEC 62053-22 und 64 Abtastungen pro Zyklus. Das Messgerät misst Energie, Wirk- und Blindleistung, Spannung, Strom, Frequenz, Leistungsfaktor und bis zur 15. Oberschwingung. Mit 4 Quadranten Energiemessung. Das Gerät funktioniert in einem 50Hz oder 60Hz Netz und akzeptiert eine Versorgungsspannung von 100 bis 415 VAC und 125 bis 250 VDC. Der Bemessungsstrom dieses Messgerätes beträgt 1 A oder 5 A und unterstützt Konfigurationen mit einer Phase und Neutralleiter, drei Phasen oder drei Phasen und Neutralleiter. Der Bereich der Messspannung zwischen den Phasen beträgt 35 bis 690 VAC bei 47 bis 63 Hz. Der Messbereich zwischen Phase und Nullleiter beträgt 20 bis 400 VAC bei 45 bis 65 Hz. Das Kommunikationsprotokoll ist Modbus RTU und ASCII 2 Drähte mit Schnittstelle RS485 Unterstützung. Das Messgerät verfügt auch über einen digitalen Impulsausgang und 33 konfigurierbare Alarme. Die Produktabmessungen sind wie folgt: Breite 96 Millimeter, Tiefe 72 Millimeter, Höhe 96 Millimeter und Produktgewicht 380 g.