| Additional features |
| Device application | Current monitoring; Partial billing |
| Power quality analysis | Total harmonic distortion; up to the 31st harmonic |
| Measured value type | apparent power Min./Max., total; active and reactive power Min./Max., total; current Min./Max., average; voltage Min./Max., average; frequency Min./Max., average; total harmonic distortion THD (I) per phase; sum of harmonic voltages THD (U) per phase; power factor Min./Max., average; apparent energy total; active and reactive energy total |
| Instrument type | Calculated neutral conductor current; active power P, P1, P2, P3; current I, I1, I2, I3; peak demand power PM, QM, SM; voltage U, U21, U32, U13, V, V1, V2, V3; current peak demand; reactive power Q, Q1, Q2, Q3; power demand P, Q, S; current unbalance; active, reactive, apparent energy (with sign, four quadrants); apparent power S, S1, S2, S3 |
| Accuracy class | Class 1 reactive energy corresponds to IEC 62053-24; Class 0.5S active energy corresponds to IEC 62053-22; Class 5 harmonic distortion (I THD & U THD) |
| Accuracy of measurement | Apparent power ± 0.5 %; Active energy ± 0.5 %; Reactive energy ± 1 %; Active power ± 0.5 %; Voltage ± 0.5 %; Power factor ± 0.01; Current ± 0.5 %; Frequency ± 0.05 % |
| Measurement current | 5…6000 mA |
| Measuring voltage | 35…480 V AC 50/60 Hz between phases; 20…277 V AC 50/60 Hz between phase and neutral; 480…999000 V AC 50/60 Hz with external VT |
| Measuring range for frequency | 45…65 Hz |
| [UH,nom] Rated operating voltage | 80 - 277 V AC 45 - 65 Hz ± 10 %; 100 - 277 V DC ± 10 % |
| Network frequency | 60 Hz; 50 Hz |
| Throughput time | 50 ms 120 V AC typical; 50 ms 230 V AC typical; 50 ms 125 V DC typical |
| [In] Rated current | 5 A; 1 A |
| Maximum power consumption in VA | 8 VA at 277 V AC |
| Max. power consumption in W | 3.3 W (power supply (AC)); 3.3 W at 277 V (power supply (DC)) |
| Input impedance | current (impedance 5 MOhm) |
| Tamper protection of settings | Protected by access code |
| Display type | Backlit display (LCD) |
| Display colour | Monochrome |
| Display resolution | 128 x 128 pixels |
| Demand intervals | Configurable from 1 to 60 minutes |
| Displayed information | Power demand (old value); Power demand (current value); Energy demand (old value); Energy demand (current value); Voltage; Current; Frequency; Energy consumption; Harmonic distortion; Power factor; Active power; Apparent power; Reactive power; Unbalance in %; Harmonic amplitude |
| Control type | 4 x button |
| Local signalling | Red LED: output signal 1 - 9.999.000 pulses/k_h (kWh, kVAh, kVARh); Green LED: module operation and integrated communication |
| Number of inputs | 0 |
| Number of outputs | 0 |
| Communications protocol | Modbus RTU at 4,800, 9,600, 19,200 BpS, 38.4 Kbit/s even/odd or none - 2-wire, insulation 2500 V |
| Support for communication interfaces | Screw terminal block: RS485 |
| Data logging | Energy consumption logs; performance logs; timestamping; Min./Max. for 8 parameters |
| Function available | Real-time clock |
| Scanning interval | 64 samples/cycle |
| Cybersecurity | Enable/disable communication ports |
| Communication service | remote monitoring |
| User language | Russian; French; Portuguese; English; Spanish; Chinese; German |
| Product certifications | CE complies with IEC 61010-1; CULus complies with UL 61010-1; CULus complies with CSA C22.2 No. 61010-1; RCM; EAC; C-Tick |
| Mounting mode | Plug-in |
| Mounting position | Vertical |
| Mounting bracket | Frame conditions |
| Supplied accessories | 1 x installation manual |
| Measurement category | Category III 480 V; Category II 480...600 V |
| Electrical insulation class | Double insulation; Class II |
| Flame retardancy | V-0 corresponds to UL 94 |
| Connections - terminals | Current transformer: screw connection (bottom) 6; voltage inputs: screw connection (top) 4 |
| Material | Polycarbonate |
| Width | 96 mm |
| Depth | Total: 76.09 mm; Integrated: 61.64 mm |
| Height | 96 mm |
| Product weight | 300 g |
| Compatibility code | PM2230 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | EasyLogic |
| Product name | EasyLogic PM2200 |
| Product or component type | Power meter |
| Device short name | PM2230 |
| Mounting |
| Lifespan | 7 years |
| Degree of protection (IP) | IP54 front: complies with IEC 60529; IP30 housing: complies with IEC 60529 |
| Relative humidity | 5…95 % at 50 °C |
| Pollution degree | 2 |
| Operating ambient temperature | -10…60 °C |
| Ambient temperature during storage | -25…70 °C |
| Over voltage category | III |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 12,500 cm |
| VPE 1 width | 9,000 cm |
| VPE 1 length | 12,000 cm |
| Packaging weight (Lbs) | 355,000 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 18 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 7,025 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 144 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 66,200 kg |
This device is a universal meter for control panel installation with a size of 96 mm x 96 mm and a backlit LCD display with 128 x 128 pixels. The universal meter measures active energy according to accuracy class 0.5S according to IEC 62053-22 with a sampling rate of 64 samples per cycle. Can measure all three power and energy values such as active, apparent and reactive power as well as voltages, currents, frequency and power factor. Plus total harmonic distortion and individual harmonics up to the 31st order. The universal meter operates with either a mains frequency of 50Hz or 60Hz and accepts universal control voltages from 80 to 300 V between phase and neutral, AC or DC. The rated current for this meter is either 1 A or 5 A at the power input. It supports up to 13 different types of wiring schemes under single-phase, two-phase or three-phase configuration types. The measuring voltage range between phases is 35 to 480 VAC phase to phase at 45 to 65 Hz, while the range between phase and neutral is 20 to 277 V. It has an RS485 communication port with Modbus RTU protocol. The meter can be upgraded with optional I/O modules for pulse monitoring. These modules have either two channels each for digital inputs and outputs or analog inputs and outputs. This version can be configured for 23 different types of alarms stored in 40 registers. The product dimensions are as follows: width 96 mm, depth 54 mm, height 96 mm and product weight 300 g.