| Additional features |
| Device application | Partial billing; Current monitoring |
| Power quality analysis | Total harmonic distortion; up to the 31st harmonic |
| Measured value type | apparent power Min./Max., total; active and reactive power Min./Max., total; current Min./Max., average; voltage Min./Max., average; frequency Min./Max., average; total harmonic distortion THD (I) per phase; sum of harmonic voltages THD (U) per phase; power factor Min./Max., average; apparent energy total; active and reactive energy total |
| Instrument type | Peak power demand; Active power P, P1, P2, P3; Power demand P, Q, S; Reactive power Q, Q1, Q2, Q3; Apparent power S, S1, S2, S3; Active, reactive, apparent energy (with sign, four quadrants); Voltage U, U21, U32, U13, V, V1, V2, V3; Current I, I1, I2, I3; Calculated neutral current; Current unbalance; Peak demand power PM, QM, SM |
| Accuracy class | Class 1 reactive energy corresponds to IEC 62053-24; Class 0.5S active energy corresponds to IEC 62053-22; Class 5 harmonic distortion (I THD & U THD) |
| Accuracy of measurement | Apparent power ± 0.5 %; Active energy ± 0.5 %; Reactive energy ± 1 %; Active power ± 0.5 %; Voltage ± 0.5 %; Power factor ± 0.01; Current ± 0.5 %; Frequency ± 0.05 % |
| Measurement current | 5…6000 mA |
| Measuring voltage | 35…480 V AC 50/60 Hz between phases; 20…277 V AC 50/60 Hz between phase and neutral; 480…999000 V AC 50/60 Hz with external VT |
| Measuring range for frequency | 45…65 Hz |
| [UH,nom] Rated operating voltage | 80 - 277 V AC 45 - 65 Hz ± 10 %; 100 - 277 V DC ± 10 % |
| Network frequency | 50 Hz; 60 Hz |
| Throughput time | 50 ms 120 V AC typical; 50 ms 230 V AC typical; 50 ms 125 V DC typical |
| [In] Rated current | 1 A; 5 A |
| Maximum power consumption in VA | 8 VA at 277 V AC |
| Max. power consumption in W | 3.3 W (power supply (AC)); 3.3 W at 277 V (power supply (DC)) |
| Input impedance | current (impedance 5 MOhm) |
| Tamper protection of settings | Protected by access code |
| Display type | 7-segment LED |
| Display colour | Red |
| Message display capacity | 3 fields with 4 characters |
| Display digits | 12 digit(s) - 14.2 mm height |
| Demand intervals | Configurable from 1 to 60 minutes |
| Displayed information | Power consumption (old value); Power consumption (current value); Energy consumption (old value); Energy consumption (current value); Voltage; Current; Frequency; Energy consumption; Harmonic distortion; Power factor; Active power; Apparent power; Reactive power; Unsymmetry in % |
| Control type | 3 x button |
| Local signalling | Red LED: output signal 1 - 9.999.000 pulses/k_h (kWh, kVAh, kVARh); Green LED: module operation and integrated communication |
| Number of inputs | 0 |
| Number of outputs | 0 |
| Communications protocol | Modbus RTU at 4,800, 9,600, 19,200 BpS, 38.4 Kbit/s even/odd or none - 2-wire, insulation 2500 V |
| Support for communication interfaces | Screw terminal block: RS485 |
| Data logging | Performance logs; timestamping; energy consumption logs; Min./Max. for 8 parameters |
| Function available | Real-time clock |
| Scanning interval | 64 samples/cycle |
| Cybersecurity | Enable/disable communication ports |
| Communication service | remote monitoring |
| Product certifications | CE complies with IEC 61010-1; CULus complies with UL 61010-1; CULus complies with CSA C22.2 No. 61010-1; RCM; EAC; C-Tick |
| Mounting mode | Plug-in |
| Mounting position | Vertical |
| Mounting bracket | Frame conditions |
| Supplied accessories | 1 x installation manual |
| Measurement category | Category III 480 V; Category II 480...600 V |
| Electrical insulation class | Class II; double insulation |
| Flame retardancy | V-0 corresponds to UL 94 |
| Connections - terminals | Current transformer: screw connection (bottom) 6; voltage inputs: screw connection (top) 4 |
| Material | Polycarbonate |
| Width | 96 mm |
| Depth | Total: 76.09 mm; Integrated: 61.64 mm |
| Height | 96 mm |
| Product weight | 300 g |
| Compatibility code | PM2130 |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | EasyLogic |
| Product name | EasyLogic PM2100 |
| Product or component type | Power meter |
| Device short name | PM2130 |
| Mounting |
| Lifespan | 7 years |
| Degree of protection (IP) | IP54 front: complies with IEC 60529; IP30 housing: complies with IEC 60529 |
| Relative humidity | 5…95 % at 50 °C |
| Pollution degree | 2 |
| Operating ambient temperature | -10…60 °C |
| Ambient temperature during storage | -25…70 °C |
| Over voltage category | III |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 11,500 cm |
| VPE 1 width | 12,000 cm |
| VPE 1 length | 12,500 cm |
| Packaging weight (Lbs) | 407,000 g |
| VPE 2 type | S03 |
| VPE 2 quantity | 18 |
| VPE 2 height | 30,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 7,726 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 144 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 71,808 kg |
Bei diesem Gerät handelt es sich um ein Universalmessgerät für den Schaltschrankeinbau mit einer Größe von 96 mm x 96 mm und einer 3-zeiligen, hellroten, 4-stelligen LED-Anzeige mit 14,2 mm Höhe. Das Universalmessgerät misst die Wirkenergie gemäß der Genauigkeitsklasse 0,5S nach IEC 62053-22 mit einer Abtastrate von 64 Abtastungen pro Zyklus. Kann alle drei Leistungs- und Energiewerte wie Wirk-, Schein- und Blindleistung sowie Spannungen, Strom, Frequenz und Leistungsfaktor messen. Plus die gesamte harmonische Verzerrung und einzelne Oberschwingungen bis zur 31. Ordnung. Das Universalmessgerät arbeitet entweder mit einer Netzfrequenz von 50Hz oder 60Hz und akzeptiert universelle Steuerspannungen von 80 bis 300 V zwischen Phase und Nullleiter, AC oder DC. Der Bemessungsstrom für dieses Messgerät beträgt entweder 1 A oder 5 A am Stromeingang. Es unterstützt bis zu 13 verschiedene Arten von Verdrahtungsschemata unter einphasigen, zweiphasigen oder dreiphasigen Konfigurationstypen. Der Bereich der Messspannung zwischen den Phasen beträgt 35 bis 480 V AC von Phase zu Phase bei 45 bis 65 Hz, während der Bereich zwischen Phase und Neutralleiter 20 bis 277 V beträgt. Es verfügt über einen RS485 Kommunikationsanschluss mit Modbus RTU Protokoll. Das Messgerät kann mit optionalen E/A Modulen für die Überwachung von Inpulsen aufgerüstet werden. Diese Module verfügen entweder über je zwei Kanäle für Digitalein- und -ausgänge oder Analogein- und -ausgänge. Diese Version kann für 23 verschiedene Arten von Alarmen konfiguriert werden, die in 40 Registern gespeichert sind. Die Produktabmessungen sind wie folgt: Breite 96 mm, Tiefe 54 mm, Höhe 96 mm und Produktgewicht 300 g.