| Additional features |
| Measured value type | voltage sags and surges; current sags and surges; voltage; current; frequency; total active and reactive power; total apparent power; active and reactive power per phase; apparent power per phase; total power factor; power factor per phase; active and reactive energy; apparent energy; harmonic distortion (I THD & U THD) |
| [UH,nom] Rated operating voltage | 20 - 60 V DC ± 10 % |
| Throughput time | 500 ms 60 V DC typical |
| Type of network | 3-pole + N + E |
| Power consumption in VA | 15 W at 20 - 60 V DC |
| Maximum power consumption in VA | 38 W at 20 - 60 V DC |
| Display type | Without display |
| Scanning interval | 1,024 samples/cycle |
| Input type | Voltage (impedance 5 MOhm); Clamp current transformer (LVCT) (impedance 200 kOhm) 5 x |
| Measuring voltage | 57…400 V AC 42 - 69 Hz between phase and neutral; 100…690 V AC 42 - 69 Hz between phases |
| Measuring range for frequency | 20…450 Hz |
| Number of inputs | 8 digital 30 V AC/60 V DC |
| Accuracy of measurement | Voltage ± 0.1 %; Current ± 0.1 % |
| Accuracy class | Class 0.1S active energy according to IEC 62053-22; Class 0.1 active energy according to IEC 61557-12; Class 0.1 active energy according to ANSI C12.20; Class 0.5S reactive energy according to IEC 62053-24; Class 0.1 current according to IEC 61557-12; Class 0.1 voltage according to IEC 61557-12; Class 0.1 active power according to IEC 61557-12; Class 0.5 power factor according to IEC 61557-12 |
| Number of outputs | 4 digital; 2 relays of form C |
| Communications protocol | Modbus RTU at 2.400 - 115.200 bit/s - 2-wire; ION at 2.400 - 115.200 bit/s - 2-wire; DNP3 at 2.400 - 115.200 bit/s - 2-wire; Modbus TCP at 10/100 Mbit/s; ION TCP at 10/100 Mbit/s; DNP3 TCP at 10/100 Mbit/s; IEC 61850; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; DHCP; DNS; DLMS |
| Support for communication interfaces | 2 RS485 removable screw terminal block |
| Ethernet connection | 10/100BASE-TX 2 RJ45 |
| Communication gateway | Ethernet/serial |
| Time synchronization protocol | GPS; IRIG-B; NTP; SNTP; PTP |
| Data logging | Timestamping; Minimum/maximum values of real-time values; User-defined data logging; Continuous logging or snapshot; Trend curves/forecasts; Event logging; Alarm logs; Configuration changes; Power failure; User login/logout; Data logs; GPS synchronisation; Event sequence logging |
| Memory capacity | 2 GB |
| Cybersecurity | Syslog protocol support; Robust security protocols; Hardening; Enable/disable communication ports; Hardware measurement lock |
| Web services | Display of captured waveform; web page; pass/fail report for IEEE 519; pass/fail report for EN 50160; ITIC (CBEMA) curve; SEMI curve; NEMA motor inrush curve; alarm notification by email; TLS 1.2; transmission of historical data by email |
| Ethernet Service | DHCP client; Device Profile Web Services (DPWS); Rapid Spanning Tree Protocol (RSTP); FTP/HTTP/HTTPS |
| Communication service | Conformity reports; Summary of power quality; Energy report; EcoStruxure Power event analysis; E-mail notification via SMTP; SNMP |
| Tamper protection of settings | Protected by tamper-proof housing |
| Mounting bracket | DIN rail |
| Electrical insulation class | Class III in accordance with EN/IEC 62052-11 |
| Insulation voltage | III400…690 V corresponds to EN 61010-1:Ed. 3; III347…600 V corresponds to UL 61010-1:Ed. 3; III347…600 V corresponds to CSA C22.2 Nr. 61010-1:Ed. 3 |
| Width | 160 mm |
| Depth | 135,3 mm |
| Height | 160 mm |
| Product weight | 1,5 kg |
| Market segment | Data centre; Healthcare; Semiconductor; Pharmacy; Chemicals; Energy; Mining |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | PowerLogic |
| Product or component type | Energy and power quality meter |
| Device short name | ION93030 |
| Product name | PowerLogic ION9000 |
| Device application | Current monitoring; S0 pulse detection for measuring water, air, gas, electricity, steam; network measurement; medium voltage; high voltage |
| Instrument type | Demand current I1, I2, I3, I4, I5; Peak demand current; Power demand P, Q, S; Peak demand power PM, QM, SM; Calculated active and reactive energy (+/- W.h, +/- VAR.h) |
| Mounting |
| Degree of protection (IP) | IP65 front: ; IP30 rear: |
| Degree of protection | UL Type 12, front side |
| Relative humidity | 5…95 % |
| Operating ambient temperature | -25…70 °C |
| Ambient temperature during storage | -40…85 °C |
| Installation category | III |
| Operating altitude | 0 - 3.000 m |
| Standards | ANSI C12.20; ANSI C37.90.1; IEC 61000-4-15; IEC 61000-4-30; IEC 61010-1; IEC 61326-1; IEC 61557-12; IEC 61850; IEC 62052-11; IEC 62052-31; IEC 62053-22; IEC 62053-23; IEC 62053-24; IEC 62586; UL 61010-1 |
| Conformity marking | ISO 9001; ISO 14000 |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 30,0 cm |
| VPE 1 width | 30,0 cm |
| VPE 1 length | 41,0 cm |
| Packaging weight (Lbs) | 2,4 kg |