| Complementary |
| Power quality analysis | EN 50160 compliance checking; conforming to IEEE 519 harmonic limit; conforming to IEC 61000-4-30: class A compliance reporting; conforming to IEEE 519 compliance reporting; waveform capture; total demand distortion; total harmonic distortion; up to the 63rd harmonic; up to the 127th harmonic with software; disturbance direction detection; dip, swell and transient; half cycle data acquisition; transient detection (20 µs) |
| Type of measurement | Voltage sags and swells; Current sags and swells; Voltage; Current; Frequency; Active and reactive power total; Apparent power total; Active and reactive power per phase; Apparent power per phase; Power factor total; Power factor per phase; Active and reactive energy; Apparent energy; Harmonic distortion (I THD & U THD) |
| [Us] rated supply voltage | 20...60 V DC +/- 10 % |
| Ride-through time | 500 ms 60 V DC typical |
| [In] rated current | 1 A; 5 A |
| type of network | 3P + N + E |
| Power consumption in VA | 15 W at 20...60 V DC |
| Maximum power consumption in VA | 38 W at 20...60 V DC |
| Display type | Without display |
| Sampling rate | 1024 samples/cycle |
| Measurement current | 0.01…20 A |
| input type | Voltage (impedance 5 MOhm); External CT (impedance 0.3 mOhm)5 x |
| Measurement voltage | 57…400 V AC 42...69 Hz between phase and neutral; 100…690 V AC 42...69 Hz between phases |
| Frequency measurement range | 20…450 Hz |
| Number of inputs | 8 digital 30 V AC/60 V DC |
| Measurement accuracy | Voltage +/- 0.1 %; Current +/- 0.1 % |
| Accuracy class | Class 0.1S active energy conforming to IEC 62053-22; Class 0.1 active energy conforming to IEC 61557-12; Class 0.1 active energy conforming to ANSI C12.20; Class 0.5S reactive energy conforming to IEC 62053-24; Class 0.1 current conforming to IEC 61557-12; Class 0.1 voltage conforming to IEC 61557-12; Class 0.1 active power conforming to IEC 61557-12; Class 0.5 power factor conforming to IEC 61557-12 |
| Number of outputs | 4 digital; 2 form C relay |
| Communication port protocol | Modbus RTU at 2400...115200 bps - 2-wire; ION at 2400...115200 bps - 2-wire; DNP3 at 2400...115200 bps - 2-wire; Modbus TCP at 10/100 Mbit/s; ION TCP at 10/100 Mbit/s; DNP3 TCP at 10/100 Mbit/s; IEC 61850; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; DHCP; DNS; DLMS |
| Communication port support | RS485 2 removable screw terminal block |
| Port Ethernet | 10/100BASE-TX 2 RJ45 |
| Communication gateway | Ethernet/serial |
| Time synchronisation protocol | GPS; IRIG-B; NTP; SNTP; PTP |
| Data recording | Time stamping; Min/max of instantaneous values; User-definable data logs; Continuous logging or snapshot; Trending/forecasting; Event logs; Alarm logs; Configuration change; Power outage; User login/logout; Data logs; GPS synchronisation; Sequence of event recording |
| Memory capacity | 2 GB |
| Cybersecurity | Syslog protocol support; Robust security logs; Port hardening; Enable/disable communication ports; Hardware metrology lock |
| Web services | Viewing of captured waveform; Web page; Pass/fail report for IEEE 519; Pass/fail report for EN 50160; ITIC (CBEMA) curve; SEMI curve; NEMA motor derating curve; Alarm notification by e-mail; TLS 1.2; Push historical data via mail |
| Ethernet service | DHCP client; Device Profile Web Services (DPWS); Rapid Scanning Tree Protocol (RSTP); FTP/HTTP/HTTPS |
| Communication service | Compliant reports; Power quality summary; Energy report; EcoStruxure Power Events Analysis; SMTP e-mail notification; SNMP |
| Tamperproof of settings | Protected by sealable cover |
| Mounting support | DIN rail |
| Electrical insulation class | Class III conforming to EN/IEC 62052-11 |
| Isolation voltage | III400…690 V conforming to EN 61010-1:ed. 3; III347…600 V conforming to UL 61010-1:ed. 3; III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3 |
| Width | 160 mm |
| Depth | 135.3 mm |
| Height | 160 mm |
| Net weight | 1.5 kg |
| Market segment | Data center; Healthcare; Semiconductor; Pharmaceutical; Chemical; Energy; Mining |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP65 front: ; IP30 rear: |
| Degree of protection | UL type 12, front |
| Relative humidity | 5…95 % |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Installation category | III |
| Operating altitude | 0...3000 m |
| Standards | ANSI C12.20; ANSI C37.90.1; IEC 61000-4-15; IEC 61000-4-30; IEC 61010-1; IEC 61326-1; IEC 61557-12; IEC 61850; IEC 62052-11; IEC 62052-31; IEC 62053-22; IEC 62053-23; IEC 62053-24; IEC 62586; UL 61010-1 |
| Quality labels | ISO 9001; ISO 14000 |
| Main |
| Range | PowerLogic |
| Product or component type | Energy and power quality meter |
| Device short name | ION92030 |
| Product name | PowerLogic ION9000 |
| Device application | Power monitoring; WAGES metering; Net metering; Medium voltage; High voltage |
| Metering type | Demand current I1, I2, I3, I4, I5; Peak demand currents; Demand power P, Q, S; Peak demand power PM, QM, SM; Calculated active and reactive energy (+/- W.h, +/- VAR.h) |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 30.0 cm |
| Package 1 Width | 30.0 cm |
| Package 1 Length | 41.0 cm |
| Package 1 Weight | 2.6 kg |