| Complementary |
| Current transformer type | Tropicalised for busbar and cable; Solid core |
| Current transformer ratio | 500/5 |
| [Ith] conventional free air thermal current | 30 kA |
| Dynamic withstand current | 2.5 Ith |
| Maximum safety factor | 5 |
| [Ue] rated operational voltage | < 720 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 3 kV |
| Mounting mode | Insulated locking screw; Clip-on; By screws |
| Mounting support | DIN rail; Busbar; Mounting plate |
| Width | Outside: 70 mm |
| Height | Outside: 95 mm |
| Depth | Frame : 45 mm; Total : 65 mm |
| Diameter | 40 mm |
| Net weight | 0.329 kg |
| [Uimp] rated impulse withstand voltage | 3 kV |
| Electrical insulation class | Class B |
| Cable outer diameter | 40 mm |
| Opening of bars | 50.5 x 12.5; 40.5 x 20.5 |
| Sealing | Without |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | VDE 0414; IEC 61869-2 |
| Product certifications | CE |
| IP degree of protection | IP20 |
| Relative humidity | 0…95 % |
| Ambient air temperature for operation | -25…60 °C |
| Logistical informations |
| Country of origin | TN |
| Main |
| Range | PowerLogic |
| Product or component type | Current transformer |
| Product name | CT |
| Secondary current | 5 A |
| Accuracy class | Class 0.5 at 4 VA; Class 1 at 6 VA |
| [In] rated current | 500 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.0 cm |
| Package 1 Width | 9.0 cm |
| Package 1 Length | 11.5 cm |
| Package 1 Weight | 339.0 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 33 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 11.674 kg |
PowerLogic. Current transformer TI, type MD - for cables up to DM 40 mm and rail profiles up to 12 x 50 / 20 x 40 mm. Transformer TI 500/5. Size_Ipn_5A 500, power VA GKl 0.5 4, power VA GKl 1 6. Dimensions (WxHxD) 70 x 95 x 65 mm. Transformer ratio of primary current lpn to secondary current Isn of 5 A for measuring devices. Rated operating voltage Ue max. 720 V, frequency 50-60 Hz. Safety factor 40-4000 A FS 95%.