Further information for Schneider Electric M9R81425 residual current circuit breaker 4-pole 25A
Complementary
Network frequency
50/60 Hz
[Ue] rated operational voltage
480Y/277 V AC 60 Hz; 415 V AC 50 Hz
Residual current tripping technology
Voltage independent
Rated breaking and making capacity
Idm 1500 A conforming to EN/IEC 61008-1
Rated conditional short-circuit current
Inc 10 kA 100 A gG
[Ui] rated insulation voltage
440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 61008-1
Control type
Toggle
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
8
Height
81 mm
Width
72 mm
Depth
60 mm
Net weight
0.45 kg
Colour
Grey (RAL 7035)
Mechanical durability
20000 cycles
Locking options description
Padlocking in OFF position
Connections - terminals
Tunnel type terminals (top or bottom)1…25 mm² (18 AWG...3 AWG) - flexible; Tunnel type terminals (top or bottom)1…35 mm² (18 AWG...2 AWG) - rigid; Tunnel type terminals (top or bottom)1…25 mm² (18 AWG...3 AWG) - flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
3.5 N.m top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…70 °C
Logistical informations
Country of origin
ES
Main
Range
Multi9
Product name
Multi9 GFP
Product or component type
Residual current circuit breaker (RCCB)
Device short name
GFP
Device application
Distribution
Poles description
4P
Neutral position
Left
[In] rated current
25 A at 40 °C conforming to EN/IEC 61008-1
Network type
AC
Earth-leakage sensitivity
26 mA conforming to UL 1053; 30 mA conforming to EN/IEC 61008-1
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A-SI (Super Immunised)
Utilisation category
AC-23A conforming to EN/IEC 61008-1
Standards
EN/IEC 61008-1; UL 1053
Product certifications
IEC; UL
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
9.200 cm
Package 1 Width
7.700 cm
Package 1 Length
8.500 cm
Package 1 Weight
376.000 g
Unit Type of Package 2
S03
Number of Units in Package 2
27
Package 2 Height
30.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
10.570 kg
ID residual current circuit breaker Multi 9 OEM GFP, 26mA UL 1053 / 30 mA IEC/EN 61008. 2-pole, nominal current 25A, type A-SI, operating voltage (Ue) 120-240V / 230-240V, insulation voltage (Ui) 440V. ID residual current circuit breakers offer protection against electric shock from direct and indirect contact and protection of systems in the event of insulation faults. They also have high electrical immunity to transient leakage currents and offer improved protection against earth faults. Type A-SI earth fault devices are ideal for damp environments or environments contaminated by aggressive substances. Trip unit technology - differential current. The ID residual current circuit breaker meets the following standards - IEC/EN 61008-1, UL 1053.