Further information for Schneider Electric M9R35240 RCD 2-pole 40 A
Complementary
Network frequency
50 Hz
[Ue] rated operational voltage
220...240 V AC 50 Hz
Residual current tripping technology
Voltage independent
Rated breaking and making capacity
Idm 400 A conforming to EN/IEC 61008-1
Rated conditional short-circuit current
Inc 10 kA
[Ui] rated insulation voltage
440 V AC 50 Hz conforming to EN/IEC 61008-1
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 61008-1
Surge current
3000 A
Control type
Toggle
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
4
Height
81 mm
Width
36 mm
Depth
73 mm
Net weight
0.23 kg
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
2000 cycles
Locking options description
Padlocking device
Connections - terminals
Tunnel type terminal (top or bottom)1…35 mm² - rigid; Tunnel type terminal (top or bottom)1…25 mm² - flexible; Tunnel type terminal (top or bottom): 3 cable(s) 16 mm² - rigid; Tunnel type terminal (top or bottom): 3 cable(s) 10 mm² - flexible; Tunnel type terminal (top or bottom)1…25 mm² - flexible with ferrule
Wire stripping length
15 mm for top or bottom connection
Tightening torque
3.5 N.m top or bottom
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3
Electromagnetic compatibility
8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-25…40 °C
Ambient air temperature for storage
-40…60 °C
Main
Range
Multi9
Product name
Multi9 ID
Product or component type
Residual current circuit breaker (RCCB)
Device short name
ID
Device application
Distribution
Poles description
2P
Neutral position
Left
[In] rated current
40 A
Network type
AC
Earth-leakage sensitivity
300 mA
Earth-leakage protection time delay
Selective
Earth-leakage protection class
Type A-SI (Super Immunised)
Standards
EN/IEC 61008-1
Product certifications
CE
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.400 cm
Package 1 Width
4.000 cm
Package 1 Length
9.000 cm
Package 1 Weight
203.900 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
9.000 cm
Package 2 Width
9.800 cm
Package 2 Length
26.000 cm
Package 2 Weight
1.292 kg
Unit Type of Package 3
S03
Number of Units in Package 3
24
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
5.655 kg
ID residual current circuit breaker Multi 9 OEM, 300mA. 2-pole, nominal current 40A, type A-SI, operating voltage (Ue) 230-240V, insulation voltage (Ui) 440V. ID residual current circuit breakers offer protection against electric shock from direct and indirect contact and fire protection in the event of insulation faults. Technology of the trip unit - differential current. The ID residual current circuit breaker meets the following standards - IEC/EN 61008-1.