Further information for Schneider Electric M9F22116 circuit breaker 1-pole 16A
Complementary
[Ue] rated operational voltage
240 V AC 50/60 Hz; 415 V AC 50/60 Hz; 60 V DC
Magnetic tripping limit
8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC
[Ics] rated service breaking capacity
2.25 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC; 20 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC; 2.25 kA 75 % conforming to GB/T 14048.2 - 415 V AC; 7.5 kA 75 % conforming to GB/T 14048.2 - 240 V AC; 20 kA 100 % conforming to GB/T 14048.2 - 60 V DC
[Ui] rated insulation voltage
500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
2
Height
81 mm
Width
18 mm
Depth
72 mm
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² (18 AWG...8 AWG) - rigid; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible with ferrule; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2.5 N.m top or bottom
Earth-leakage protection
Without
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…80 °C
Logistical informations
Country of origin
FR
Main
Range
Multi9
Product name
Multi9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60SP
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
16 A at 25 °C conforming to EN/IEC 60947-2
Network type
DC; AC
Trip unit technology
Thermal-magnetic
Curve code
C
Standards
EN/IEC 60947-2; GB/T 14048.2; UL 1077; CSA C22.2 No 235
Product certifications
IEC; CCC; UR; CSA
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.500 cm
Package 1 Width
1.800 cm
Package 1 Length
8.500 cm
Package 1 Weight
114.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
12
Package 2 Height
7.600 cm
Package 2 Width
8.800 cm
Package 2 Length
22.500 cm
Package 2 Weight
1.413 kg
Unit Type of Package 3
S03
Number of Units in Package 3
144
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
17.294 kg
Circuit breaker C60BP Multi 9 OEM, 10 kA. 2-pole, nominal current 1A, C characteristic, operating voltage (Ue) 240V AC IEC/EN 60947-2 / 277V AC UL 489, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60SP complies with the following standards - IEC/EN 60947-2, UL 489 / CSA C22.2 No.5 / GB 14048-2. C60SP circuit breakers are multi-standard circuit breakers that can be used worldwide because they comply with all international and all important national standards.