[Ue] rated operational voltage
240 V AC 50/60 Hz; 415 V AC 50/60 Hz; 440 V AC 50/60 Hz
Magnetic tripping limit
4 x In +/- 20 % AC; 5.7 x In +/- 20 % DC
[Ics] rated service breaking capacity
4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC; 15 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC; 4.5 kA 75 % conforming to GB/T 14048.2 - 440 V AC; 7.5 kA 75 % conforming to GB/T 14048.2 - 415 V AC; 15 kA 75 % conforming to GB/T 14048.2 - 240 V AC
[Ui] rated insulation voltage
500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
4
Height
81 mm
Width
36 mm
Depth
72 mm
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² (18 AWG...8 AWG) - rigid; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible with ferrule; Tunnel type terminal (top or bottom)1…16 mm² (18 AWG...8 AWG) - flexible
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2.5 N.m top or bottom
Earth-leakage protection
Without
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…80 °C
Logistical informations
Country of origin
FR
Main
Range
Multi9
Product name
Multi9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60SP
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
16 A at 25 °C conforming to EN/IEC 60947-2
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
B
Standards
EN/IEC 60947-2; GB/T 14048.2; UL 1077; CSA C22.2 No 235
Product certifications
IEC; CCC; UR; CSA
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.500 cm
Package 1 Width
3.600 cm
Package 1 Length
8.500 cm
Package 1 Weight
227.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
8.000 cm
Package 2 Width
9.000 cm
Package 2 Length
22.500 cm
Package 2 Weight
1.402 kg
Unit Type of Package 3
S03
Number of Units in Package 3
72
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
17.395 kg
The M9F21216 circuit breaker from the Multi 9 series by Schneider Electric is a two-pole (2P) switch with a rated current of 16 A at 25 °C, specified according to EN/IEC 60947-2. It is designed for the distribution and protection of electrical circuits in installations and is suitable for use in alternating and direct current networks. The tripping technology is based on a thermomagnetic principle, where the B characteristic (B curve) ensures selective disconnection in case of overload and short circuit. The magnetic tripping threshold is 4 times the rated current (In) for alternating voltage and 5.7 times In for direct voltage, enabling reliable response to sudden current surges.
Applications
The switch is designed for use in distribution systems, particularly in industrial, commercial, and residential buildings, where safe power distribution and protection functions are required. It is rated for operating voltages of 240 V, 415 V, and 440 V AC and complies with international standards such as EN/IEC 60947-2, UL 1077, and CSA C22.2 No 235. The rated insulation voltage is 500 V AC, ensuring safe insulation even at higher voltages. The rated impulse withstand voltage of 6 kV protects the device against transient voltage surges.
Functions and Equipment in Detail
The switch features a contact position indicator that visually signals the ON/OFF state. Operation is performed via a toggle switch, enabling simple handling. Mounting is tool-free on a DIN rail, with the device secured using a clip fastening. Connections are made via tunnel terminals on the top and bottom of the device, suitable for cable cross-sections of 1 to 25 mm² (solid) and 1 to 16 mm² (flexible, with or without wire end ferrule). The wire stripping length is 14 mm, and the required tightening torque is 2.5 Nm.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and a magnetic tripping mechanism: the thermal part responds to prolonged overloads, while the magnetic part rapidly disconnects in case of sudden short circuits. The snap-action switching ensures wear-free switching of contacts, increasing the service life. The mechanical life is 20,000 cycles, and the electrical life is 10,000 cycles. The device is designed for operating temperatures from -30 °C to 70 °C and can be used up to an altitude of 2,000 m above sea level. Storage is possible from -40 °C to 80 °C.
Compatibility and Accessories
The switch is modular and can be extended with various auxiliary modules that can be mounted on the DIN rail. These include auxiliary contacts (e.g. M9A26917, M9A26914), load current release units (e.g. M9A26946, M9A26476), under-voltage release units (e.g. M9A27108, M9A27107), and residual current circuit breakers (e.g. M9R11225, M9R81225). These modules allow for functional extensions, such as signaling switching states, monitoring load current, or protection against under-voltage. Locking elements (e.g. MGN26380, MGN26381) and rotary operating handles (e.g. 27048) can also be combined to enhance safety and operability.
Mounting and Installation
Mounting is done on a DIN rail using a clip fastening, enabling tool-free and quick installation. The device is intended for mounting in enclosures or distributors and complies with protection class IP20 (IEC 60529), while modular enclosures allow for IP40. The pollution degree is 3, permitting use in environments with increased pollution risk. Drip-proofing is specified at level 2 according to IEC 60068-1.
Operational Advantages
The switch offers high reliability through thermomagnetic tripping technology and snap-action switching. Modular expandability allows adaptation to specific requirements without changing the base device. Tool-free mounting and clear indication of switching position simplify installation and maintenance. Compliance with international standards (IEC, UL, CSA, GB) enables worldwide use in various markets. The locking function supports safety during maintenance work.