Schneider Electric M9F14332, EAN: 3606480577338

Schneider Electric M9F14332 circuit breaker 3-pole 32A

Installation > Modular devices / equipment installation > Circuit breaker

Schneider Electric M9F14332 circuit breaker 3-pole 32A

Lieske Part No. 326479
Mfg Part No M9F14332
EAN-Code 3606480577338
Manufacturer Schneider Electric
Here only 178,60 EUR
212,53 EUR incl. VAT

Further information for Schneider Electric M9F14332 circuit breaker 3-pole 32A

Complementary
[Ue] rated operational voltage240 V AC 50/60 Hz between phases; 415 V AC 50/60 Hz between phases; 440 V AC 50/60 Hz between phases;
Magnetic tripping limit8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC
[Ics] rated service breaking capacity15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz; 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz; 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 40 kA 100 % conforming to EN/IEC 60947-2 -
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2
Control typeToggle
Local signallingON/OFF indication
Mounting modeClip-on
Mounting supportDIN rail
9 mm pitches6
Height81 mm
Width54 mm
Depth72 mm
Net weight0.36 kg
ColourGrey
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Connections - terminalsTunnel type terminal (top or bottom)1.5…35 mm² - rigid; Tunnel type terminal (top or bottom)1.5…35 mm² - flexible; Tunnel type terminal (top or bottom)1.5…35 mm² - flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Tightening torque3.5 N.m top or bottom
Earth-leakage protectionSeparate block
Contact position indicatorYes
Contractual warranty
Warranty (in months)18
Environment
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…80 °C
Logistical informations
Country of originFR
Main
RangeMulti9
Product nameMulti9 C60
Product or component typeMiniature circuit-breaker
Device short nameC60H
Device applicationDistribution
Poles description3P
Number of protected poles3
[In] rated current32 A at 50 °C conforming to EN/IEC 60947-2
Network typeDC; AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Curve codeC
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 15 kA Icu at 415 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 10 kA Icu at 440 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 40 kA Icu at
Utilisation categoryCategory A conforming to EN/IEC 60947-2
StandardsEN/IEC 60947-2; GB/T 14048.2
Product certificationsEAC; CCC
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height5.4 cm
Package 1 Width7.5 cm
Package 1 Length8.5 cm
Package 1 Weight356 g
Unit Type of Package 2BB1
Number of Units in Package 24
Package 2 Height8 cm
Package 2 Width9 cm
Package 2 Length22.5 cm
Package 2 Weight1.472 kg
Unit Type of Package 3S03
Number of Units in Package 324
Package 3 Height30 cm
Package 3 Width30 cm
Package 3 Length40 cm
Package 3 Weight9.35 kg
Circuit breaker C60SP Multi 9 OEM, 5 kA. 2-pole, nominal current 50A, B characteristic, operating voltage (Ue) 415V AC IEC/EN 60947-2 / 277V AC UL 1077, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60SP complies with the following standards - IEC/EN 60947-2, UL 1077 / CSA C22.2 No.235 / GB 14048-2. C60SP circuit breakers are multi-standard circuit breakers that can be used worldwide because they comply with all international and all important national standards.