Further information for Schneider Electric M9F14320 circuit breaker 3-pole 20A
Complementary
[Ue] rated operational voltage
240 V AC 50/60 Hz between phases; 415 V AC 50/60 Hz between phases; 440 V AC 50/60 Hz between phases;
Magnetic tripping limit
8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC
[Ics] rated service breaking capacity
15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz; 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz; 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 40 kA 100 % conforming to EN/IEC 60947-2 -
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
6
Height
81 mm
Width
54 mm
Depth
72 mm
Net weight
0.36 kg
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² - rigid; Tunnel type terminal (top or bottom)1…25 mm² - flexible; Tunnel type terminal (top or bottom)1…25 mm² - flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…80 °C
Logistical informations
Country of origin
FR
Main
Range
Multi9
Product name
Multi9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60H
Device application
Distribution
Poles description
3P
Number of protected poles
3
[In] rated current
20 A at 50 °C conforming to EN/IEC 60947-2
Network type
AC; DC
Network frequency
50/60 Hz
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
30 kA Icu at 240 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 15 kA Icu at 415 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 10 kA Icu at 440 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 40 kA Icu at
Utilisation category
Category A conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2; GB/T 14048.2
Product certifications
EAC; CCC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.5 cm
Package 1 Width
5.4 cm
Package 1 Length
8.5 cm
Package 1 Weight
334 g
Unit Type of Package 2
BB1
Number of Units in Package 2
4
Package 2 Height
8 cm
Package 2 Width
9 cm
Package 2 Length
22.5 cm
Package 2 Weight
1.388 kg
Unit Type of Package 3
S03
Number of Units in Package 3
48
Package 3 Height
30 cm
Package 3 Width
30 cm
Package 3 Length
40 cm
Package 3 Weight
17.369 kg
Circuit breaker C60SP Multi 9 OEM, 5 kA. 2-pole, nominal current 40A, B characteristic, operating voltage (Ue) 415V AC IEC/EN 60947-2 / 277V AC UL 1077, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60SP complies with the following standards - IEC/EN 60947-2, UL 1077 / CSA C22.2 No.235 / GB 14048-2. C60SP circuit breakers are multi-standard circuit breakers that can be used worldwide because they comply with all international and all important national standards.