Further information for Schneider Electric M9F12216 circuit breaker 2-pole 16A
Complementary
[Ue] rated operational voltage
240 V AC 50/60 Hz between phases; 415 V AC 50/60 Hz between phases; 440 V AC 50/60 Hz between phases;
Magnetic tripping limit
12 x In +/- 20 % AC; 17 x In +/- 20 % DC
Breaking capacity
20 kA Icu at 240 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 10 kA Icu at 415 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 20 kA Icu at
[Ics] rated service breaking capacity
16 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz; 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 20 kA 100 % conforming to EN/IEC 60947-2 -
Limitation class
3
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
4
Height
81 mm
Width
36 mm
Depth
72 mm
Net weight
0.24 kg
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² - rigid; Tunnel type terminal (top or bottom)1…25 mm² - flexible; Tunnel type terminal (top or bottom)1…25 mm² - flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…80 °C
Logistical informations
Country of origin
BG
Main
Range
Multi9
Product name
Multi9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60N
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
16 A at 50 °C conforming to EN/IEC 60947-2
Network type
DC; AC
Network frequency
50/60 Hz
Trip unit technology
Thermal-magnetic
Curve code
D
Utilisation category
Category A conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2; GB/T 14048.2
Product certifications
EAC; KC; CCC
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.300 cm
Package 1 Width
3.500 cm
Package 1 Length
8.500 cm
Package 1 Weight
209.000 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
8.000 cm
Package 2 Width
8.800 cm
Package 2 Length
22.200 cm
Package 2 Weight
1.296 kg
Unit Type of Package 3
S03
Number of Units in Package 3
72
Package 3 Height
30.000 cm
Package 3 Width
30.000 cm
Package 3 Length
40.000 cm
Package 3 Weight
16.122 kg
C60H Multi 9 OEM circuit breaker, 15 kA (IEC/EN 60947-2). 1-pole, nominal current 13A, D characteristic, operating voltage (Ue) 240V AC / 72V DC, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. C60 circuit breakers are designed for a long service life and heavily used industrial environments. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60H complies with the following standards: IEC60947-2.