Schneider Electric M9F11316, EAN: 3606480576386

Schneider Electric M9F11316 circuit breaker 3-pole 16A

Installation > Modular devices / equipment installation > Circuit breaker

Schneider Electric M9F11316 circuit breaker 3-pole 16A

Lieske Part No. 1863779
Mfg Part No M9F11316
EAN-Code 3606480576386
Manufacturer Schneider Electric
Here only 121,13 EUR
144,14 EUR incl. VAT

Further information for Schneider Electric M9F11316 circuit breaker 3-pole 16A

Complementary
[Ue] rated operational voltage240 V AC 50/60 Hz between phases; 415 V AC 50/60 Hz between phases; 440 V AC 50/60 Hz between phases;
Magnetic tripping limit8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC
Breaking capacity20 kA Icu at 240 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 10 kA Icu at 415 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 6 kA Icu at 440 V AC 50/60 Hz between phases conforming to EN/IEC 60947-2; 30 kA Icu at
[Ics] rated service breaking capacity16 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz; 7.5 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz; 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz; 30 kA 100 % conforming to EN/IEC 60947-2 -
Limitation class3
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to EN/IEC 60947-2
Control typeToggle
Local signallingON/OFF indication
Mounting modeClip-on
Mounting supportDIN rail
9 mm pitches6
Height81 mm
Width54 mm
Depth72 mm
Net weight0.36 kg
ColourGrey
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Connections - terminalsTunnel type terminal (top or bottom)1…25 mm² - rigid; Tunnel type terminal (top or bottom)1…25 mm² - flexible; Tunnel type terminal (top or bottom)1…25 mm² - flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionSeparate block
Contact position indicatorYes
Contractual warranty
Warranty (in months)18
Environment
IP degree of protectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…80 °C
Logistical informations
Country of originBG
Main
RangeMulti9
Product nameMulti9 C60
Product or component typeMiniature circuit-breaker
Device short nameC60N
Device applicationDistribution
Poles description3P
Number of protected poles3
[In] rated current16 A at 50 °C conforming to EN/IEC 60947-2
Network typeDC; AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to EN/IEC 60947-2
StandardsEN/IEC 60947-2; GB/T 14048.2
Product certificationsEAC; KC; CCC
Quality labelsUKCA; RCM
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height5.400 cm
Package 1 Width7.500 cm
Package 1 Length8.500 cm
Package 1 Weight314.000 g
Unit Type of Package 2BB1
Number of Units in Package 24
Package 2 Height8.000 cm
Package 2 Width8.800 cm
Package 2 Length22.000 cm
Package 2 Weight1.302 kg
Unit Type of Package 3S03
Number of Units in Package 348
Package 3 Height30.000 cm
Package 3 Width30.000 cm
Package 3 Length40.000 cm
Package 3 Weight16.111 kg
C60H Multi 9 OEM circuit breaker, 15 kA (IEC/EN 60947-2). 2-pole, nominal current 3A, C characteristic, operating voltage (Ue) 415V AC / 125V DC, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. C60 circuit breakers are designed for a long service life and heavily used industrial environments. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60H complies with the following standards: IEC60947-2.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1863779
qrcode für Schneider Electric M9F11316 circuit breaker 3-pole 16A