Further information for Schneider Electric M9C01203 circuit breaker 2-pole 3A
Complementary
[Ue] rated operational voltage
240 V AC 50/60 Hz between phases; 415 V AC 50/60 Hz between phases; 125 V DC
Magnetic tripping limit
8.5 x In +/- 20 % AC; 12 x In +/- 20 % DC
[Ics] rated service breaking capacity
50 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz; 30 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC; 50 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail
9 mm pitches
4
Height
81 mm
Width
36 mm
Depth
72 mm
Net weight
0.24 kg
Colour
Grey
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Provision for padlocking
Padlockable
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² - rigid; Tunnel type terminal (top or bottom)1…25 mm² - flexible; Tunnel type terminal (top or bottom)1…25 mm² - flexible with ferrule
Wire stripping length
14 mm for top or bottom connection
Tightening torque
2 N.m top or bottom
Earth-leakage protection
Separate block
Contact position indicator
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Ambient air temperature for operation
-30…70 °C
Ambient air temperature for storage
-40…80 °C
Main
Range
Multi9
Product name
Multi9 C60
Product or component type
Miniature circuit-breaker
Device short name
C60CTRL
Device application
Distribution
Poles description
2P
Number of protected poles
2
[In] rated current
3 A
Network type
AC; DC
Network frequency
50/60 Hz
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
100 kA Icu at 240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 30 kA Icu at 125 V DC conforming to EN/IEC 60947-2; 100 kA Icu at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation category
Category A conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2
Product certifications
CE
Quality labels
UKCA; RCM
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.5 cm
Package 1 Width
3.6 cm
Package 1 Length
8.5 cm
Package 1 Weight
221 g
Unit Type of Package 2
BB1
Number of Units in Package 2
6
Package 2 Height
7.8 cm
Package 2 Width
8.7 cm
Package 2 Length
22.5 cm
Package 2 Weight
1.369 kg
Unit Type of Package 3
S03
Number of Units in Package 3
72
Package 3 Height
30 cm
Package 3 Width
30 cm
Package 3 Length
40 cm
Package 3 Weight
16.915 kg
C60N Multi 9 OEM circuit breaker, 10 kA (IEC/EN 60947-2). 1-pole, nominal current 25A, D characteristic, operating voltage (Ue) 415V AC / 72V DC, insulation voltage (Ui) 500V AC. Single connection terminal for cable and pin comb bar on the top and bottom of the device. Fastened using a normal clip fastener on a DIN rail. Snap action for low-wear switching of the contacts. C60 circuit breakers are designed for a long service life and heavily used industrial environments. Technology of the trip unit - thermomagnetic. Additional auxiliary modules that can be added in series (optional) - display of switch position (OF), fault tripping (SD), shunt release (MX, MX+OF), undervoltage release (MN, MNs, MNx). Tool-free installation on the left side of the device. The C60N complies with the following standards: IEC60947-2.