| Additional features |
| Power losses (max) | 150 W |
| Inductance value | 6,489 mH |
| Inductance tolerance | - 5 % to 5 % per phase |
| Base rated current | 18 A |
| RMS current | 18,4 A |
| Electrical insulation class | Class H |
| [Ui] Rated insulation voltage | 1,1 kV |
| Dielectric test voltage | 4 kV 50 Hz 1 minute |
| [Imp] max. continuous current | 1,12 x I1 |
| Harmonic current spectrum | 5,5 % x I3; 10,7 % x I5; 5,3 % x I7; 2,1 % x I11 |
| Dynamic holding current | 2.2 x Isc |
| [Ith] conventional thermal current in free air | 2 A at 250 V AC 50 Hz |
| Installation type | Indoor installation |
| Cooling type | forced convection |
| Connections - terminals | Terminal block |
| Mounting centre | 200 x 125 mm |
| Height | 220 mm |
| Width | 240 mm |
| Depth | 160 mm |
| Product weight | 14,5 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | PowerLogic |
| Device short name | DR |
| Product or component type | Detuned choke |
| Network frequency | 50 Hz |
| Reactive power indication | 12.5 kvar for 400 V AC 50 Hz |
| Supply voltage | 400 V AC 50 Hz |
| Adjustment sequence | 2,7 - 135 Hz - 14 % - 50 Hz |
| Mounting |
| Standards | IEC 60068 |
| Degree of protection (IP) | IP00 |
| Operating ambient temperature | 0…55 °C at = 1,000 m; 0…50 °C at > 1,000 - 2,000 m |
| Average ambient air temperature for operation | 50°C at = 1,000 m (average over 24 hours); 40°C at = 1,000 m (average over 1 year); 45°C at > 1,000 - 2,000 m (average over 24 hours); 35°C at > 1,000 - 2,000 m (average over 1 year) |
| Climate resistance | Relative humidity: 20 - 80 %; salt spray (400 V/50 Hz): 250 hours |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 24,500 cm |
| VPE 1 width | 29,000 cm |
| VPE 1 length | 30,500 cm |
| Packaging weight (Lbs) | 13,800 kg |
| VPE 2 type | P12 |
| VPE 2 quantity | 24 |
| VPE 2 height | 80,000 cm |
| VPE 2 width | 80,000 cm |
| VPE 2 length | 120,000 cm |
| VPE 2 weight | 343,200 kg |
PowerLogic PFC filter circuit chokes are designed to protect the capacitor by preventing the increase of harmonics present in the system. Capacitors and chokes are configured in series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This choke is designed for 12.5 kvar output power with detuning factor of 14% (2.7/135 Hz) at 400V AC at 50 Hz. Relative impedance, 14%. This component complies with IEC 60068. This component requires additional convection, that is, a fan must be added. The dimensions of the housing are 220 mm in height, 240 mm in width and 160 mm in depth. For a product weight of 14.5 kg.