Schneider Electric LVR07X00A40T, EAN: 3606480541537

Schneider Electric LVR07X00A40T filter choke 400 V 100 kVar

Schneider Electric LVR07X00A40T filter choke 400 V 100 kVar

Lieske Part No. 1856773
Mfg Part No LVR07X00A40T
EAN-Code 3606480541537
Manufacturer Schneider Electric
Here only 1.270,15 EUR
1.511,48 EUR incl. VAT

Further information for Schneider Electric LVR07X00A40T filter choke 400 V 100 kVar

Complementary
power losses (max)480 W
Value of inductance0.375 mH
Inductance tolerance- 5 % to 5 % per phase
Fundamental current rating144.3 A
RMS current rating155.9 A
Electrical insulation classClass H
[Ui] rated insulation voltage1.1 kV
Dielectric test voltage4 kV 50 Hz 1 minute
[Imp] maximum permanent current1.2 x I1
Harmonic current spectrum3.7 % x I3; 38.2 % x I5; 13.6 % x I7; 4.9 % x I11
Dynamic withstand current2.2 x Isc
[Ith] conventional free air thermal current2 A at 250 V AC 50 Hz
Type of installationIndoor installation
Type of coolingForced convection
Connections - terminalsPad terminal
fixing center200 x 125 mm
Height350 mm
Width350 mm
Depth220 mm
Net weight37 kg
Contractual warranty
Warranty (in months)18
Environment
StandardsIEC 60068
IP degree of protectionIP00
Ambient air temperature for operation0…55 °C at 1000...2000 m
Average ambient air temperature for operation50 °C at 1000...2000 m (average over 1 year)
Climatic withstandRelative humidity: 20...80 %; Salt mist (400 V/50 Hz) : 250 hours
Logistical informations
Country of originCZ
Main
RangePowerLogic
Device short nameDR
Product or component typeDetuned reactor
Network frequency50 Hz
Reactive power rating100 kvar for 400 V AC 50 Hz
Network rated voltage400 V AC 50 Hz
Tuning order3.8 - 190 Hz - 7 % - 50 Hz
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height56.0 cm
Package 1 Width40.0 cm
Package 1 Length60.0 cm
Package 1 Weight44.0 kg
Unit Type of Package 2P06
Number of Units in Package 22
Package 2 Height50.0 cm
Package 2 Width80.0 cm
Package 2 Length60.0 cm
Package 2 Weight96.5 kg
PowerLogic PFC filter circuit chokes are designed to protect the capacitor by preventing the increase of harmonics present in the system. Capacitors and chokes are configured in series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This choke is designed for 100 kvar output power with detuning factor of 7% (3.8/190 Hz) at 400V AC and 50 Hz. Relative impedance, 7%. This component complies with IEC 60068. This component requires additional convection, that is, a fan must be added. The dimensions of the housing are 350 mm in height, 350 mm in width and 220 mm in depth. For a product weight of 37 kg.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1856773
qrcode für Schneider Electric LVR07X00A40T filter choke 400 V 100 kVar