| Complementary |
| power losses (max) | 200 W |
| Value of inductance | 1.499 mH |
| Inductance tolerance | - 5 % to 5 % per phase |
| Fundamental current rating | 36.1 A |
| RMS current rating | 39 A |
| Electrical insulation class | Class H |
| [Ui] rated insulation voltage | 1.1 kV |
| Dielectric test voltage | 4 kV 50 Hz 1 minute |
| [Imp] maximum permanent current | 1.2 x I1 |
| Harmonic current spectrum | 3.7 % x I3; 38.2 % x I5; 13.6 % x I7; 4.9 % x I11 |
| Dynamic withstand current | 2.2 x Isc |
| [Ith] conventional free air thermal current | 2 A at 250 V AC 50 Hz |
| Type of installation | Indoor installation |
| Type of cooling | Forced convection |
| Connections - terminals | Pad terminal |
| fixing center | 200 x 125 mm |
| Height | 220 mm |
| Width | 240 mm |
| Depth | 160 mm |
| Net weight | 15 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60068 |
| IP degree of protection | IP00 |
| Ambient air temperature for operation | 0…55 °C at 1000...2000 m |
| Average ambient air temperature for operation | 50 °C at 1000...2000 m (average over 1 year) |
| Climatic withstand | Relative humidity: 20...80 %; Salt mist (400 V/50 Hz) : 250 hours |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | PowerLogic |
| Device short name | DR |
| Product or component type | Detuned reactor |
| Network frequency | 50 Hz |
| Reactive power rating | 25 kvar for 400 V AC 50 Hz |
| Network rated voltage | 400 V AC 50 Hz |
| Tuning order | 3.8 - 190 Hz - 7 % - 50 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 25.000 cm |
| Package 1 Width | 29.500 cm |
| Package 1 Length | 31.000 cm |
| Package 1 Weight | 14.316 kg |
| Unit Type of Package 2 | P12 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 105.000 cm |
| Package 2 Width | 80.000 cm |
| Package 2 Length | 120.000 cm |
| Package 2 Weight | 400.000 kg |
PowerLogic PFC filter circuit chokes are designed to protect the capacitor by preventing the increase of harmonics present in the system. Capacitors and chokes are configured in series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This choke is designed for 25 kvar output power with detuning factor of 7% (3.8/190 Hz) at 400 VAC and 50 Hz. Relative impedance, 7%. This component complies with IEC 60068. This component requires additional convection, that is, a fan must be added. The dimensions of the housing are 220 mm in height, 240 mm in width and 160 mm in depth. For a product weight of 15 kg.