Additional features [Uimp] Rated impulse voltage withstand 8 kV corresponds to EN/IEC 60947-2 Network frequency 50/60 Hz Breaking capacity N [Ics] Rated operational breaking capacity 70 kA at 220/240 V AC 50/60 Hz corresponds to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz corresponds to IEC 60947-2; 32 kA at 440 V AC 50/60 Hz corresponds to IEC 60947-2 Mechanical life 15000 cycles Electrical lifetime 4000 cycles 415 V In, complies with IEC 60947-2 Control type Toggle switch Adjustable range for thermal protection 420…600 A [Ir] type of long-time pickup setting Adjustable Adjustment range for long exposure 0,7 - 1 x In Type of long-time delay setting Fixed [Ii] type of instantaneous short-circuit setting Adjustable Adjustment range of instantaneous short circuit 4 - 8 x In Mounting bracket Rear panel Mounting mode Fixed Connection on top side front side Connection on underside front side Connections - terminals Screwed connection Terminal pitch 45 mm Compatibility code CVS630 Width 140 mm Depth 110 mm Height 255 mm Product weight 5,2 kg Contact position indicator Ja Contractual warranty Warranty (in months) 18 Main features Product series EasyPacT Product name EasyPacT CVS Device short name CVS630N Product or component type Power-cut-out switch Device application Distribution Pole description 3P Description of protected poles 3D Earth fault protection (Vigi Add On) None [In] Rated current 600 A at 40 °C Type of network AC Application category Category A Rated ultimate short-circuit breaking capacity [Icu] 70 kA Icu at 220/240 V AC 50/60 Hz per IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2; 42 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2 Trigger name TM-D Trigger technology Thermal-magnetic Trigger power 600 A at 40 °C Degree of protection Short-circuit protection (magnetic); overload protection (thermal) Mounting Standards IEC 60947-2; EN 60947-2 Product certifications GOST; IEC Protection class for electric shocks Class II Pollution degree 3 entspricht IEC 60664-1 Degree of protection (IP) IP40 Operating ambient temperature -25…70 °C Ambient temperature during storage -50…85 °C Packaging units VPE 1 type PCE Number of devices per package 1 VPE 1 height 14,900 cm VPE 1 width 15,600 cm VPE 1 length 28,900 cm Packaging weight (Lbs) 5,325 kg VPE 2 type S04 VPE 2 quantity 3 VPE 2 height 30,000 cm VPE 2 width 40,000 cm VPE 2 length 60,000 cm VPE 2 weight 16,735 kg