Additional features [Uimp] Rated impulse voltage withstand 8 kV corresponds to EN/IEC 60947-2 Network frequency 50/60 Hz Breaking capacity B [Ics] Rated operational breaking capacity 15 kA at 440 V AC 50/60 Hz conforms to IEC 60947-2; 25 kA at 380/415 V AC 50/60 Hz conforms to IEC 60947-2; 40 kA at 220/240 V AC 50/60 Hz conforms to IEC 60947-2 Neutral position Left Mechanical life 20000 cycles Electrical lifetime 10000 cycles 415 V In corresponds to IEC 60947-2 Control type Toggle switch Adjustable range for thermal protection 140…200 A Neutral conductor protection setting 1 x Ir (4D) [Ir] type of long-time pickup setting Adjustable Adjustment range for long exposure 0,7 - 1 x In Type of long-time delay setting Fixed [Ii] type of instantaneous short-circuit setting Fixed Adjustment range of instantaneous short circuit 2.000 A Mounting bracket Rear panel Mounting mode Fixed Connection on top side front side Connection on underside front side Connections - terminals Screwed connection Terminal pitch 35 mm Compatibility code CVS250 Width 140 mm Depth 86 mm Height 161 mm Product weight 2,2 kg Contact position indicator Ja Contractual warranty Warranty (in months) 18 Main features Product series EasyPacT Product name EasyPacT CVS Device short name CVS250B Product or component type Power-cut-out switch Device application Distribution Pole description 4P Description of protected poles 4D Earth fault protection (Vigi Add On) None [In] Rated current 200 A at 40 °C Type of network AC Application category Category A Rated ultimate short-circuit breaking capacity [Icu] 40 kA Icu at 220/240 V AC 50/60 Hz complies with IEC 60947-2; 25 kA Icu at 380/415 V AC 50/60 Hz complies with IEC 60947-2; 20 kA Icu at 440 V AC 50/60 Hz complies with IEC 60947-2 Trigger name TM-D Trigger technology Thermal-magnetic Trigger power 200 A at 40 °C Degree of protection Short-circuit protection (magnetic); overload protection (thermal) Mounting Standards IEC 60947-2; EN 60947-2 Product certifications GOST; IEC Protection class for electric shocks Class II Pollution degree 3 entspricht IEC 60664-1 Degree of protection (IP) IP40 Operating ambient temperature -25…70 °C Ambient temperature during storage -50…85 °C Packaging units VPE 1 type PCE Number of devices per package 1 VPE 1 height 13,500 cm VPE 1 width 14,700 cm VPE 1 length 19,000 cm Packaging weight (Lbs) 2,557 kg VPE 2 type S04 VPE 2 quantity 4 VPE 2 height 30,000 cm VPE 2 width 40,000 cm VPE 2 length 60,000 cm VPE 2 weight 10,978 kg VPE 3 type P12 VPE 3 quantity 16 VPE 3 height 45,000 cm VPE 3 width 80,000 cm VPE 3 length 120,000 cm VPE 3 weight 55,912 kg