Schneider Electric LV516331, EAN: 3606480229183

Schneider Electric LV516331 power circuit breaker 3P 36 kA

Schneider Electric LV516331 power circuit breaker 3P 36 kA

Lieske Part No. 1015855
Mfg Part No LV516331
EAN-Code 3606480229183
Manufacturer Schneider Electric
Here only 400,09 EUR
476,11 EUR incl. VAT

Further information for Schneider Electric LV516331 power circuit breaker 3P 36 kA

Additional features
[Uimp] Rated impulse voltage withstand8 kV corresponds to EN/IEC 60947-2
Network frequency50/60 Hz
Breaking capacityF
[Ics] Rated operational breaking capacity18 kA at 440 V AC 50/60 Hz according to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz according to IEC 60947-2; 70 kA at 220/240 V AC 50/60 Hz according to IEC 60947-2
Mechanical life25000 cycles
Electrical lifetime12000 cycles 415 V In corresponds to IEC 60947-2
Control typeToggle switch
Adjustable range for thermal protection70…100 A
[Ir] type of long-time pickup settingAdjustable
Adjustment range for long exposure0,7 - 1 x In
Type of long-time delay settingFixed
[Ii] type of instantaneous short-circuit settingFixed
Adjustment range of instantaneous short circuit800 A
Mounting bracketRear panel
Mounting modeFixed
Connection on top sidefront side
Connection on undersidefront side
Connections - terminalsScrewed connection
Terminal pitch35 mm
Compatibility codeCVS160
Width105 mm
Depth86 mm
Height161 mm
Product weight1,5 kg
Contact position indicatorJa
Contractual warranty
Warranty (in months)18
Main features
Product seriesEasyPacT
Product nameEasyPacT CVS
Device short nameCVS160F
Product or component typePower-cut-out switch
Device applicationDistribution
Pole description3P
Description of protected poles3D
Earth fault protection (Vigi Add On)None
[In] Rated current100 A at 40 °C
Type of networkAC
Application categoryCategory A
Rated ultimate short-circuit breaking capacity [Icu]36 kA Icu at 440 V AC 50/60 Hz, complies with IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz, complies with IEC 60947-2; 70 kA Icu at 220/240 V AC 50/60 Hz, complies with IEC 60947-2
Trigger nameTM-D
Trigger technologyThermal-magnetic
Trigger power100 A at 40 °C
Degree of protectionShort-circuit protection (magnetic); overload protection (thermal)
Mounting
StandardsIEC 60947-2; EN 60947-2
Product certificationsGOST; IEC
Protection class for electric shocksClass II
Pollution degree3 entspricht IEC 60664-1
Degree of protection (IP)IP40
Operating ambient temperature-25…70 °C
Ambient temperature during storage-50…85 °C
Packaging units
VPE 1 typePCE
Number of devices per package1
VPE 1 height11,000 cm
VPE 1 width14,000 cm
VPE 1 length19,000 cm
Packaging weight (Lbs)1,728 kg
VPE 2 typeS03
VPE 2 quantity7
VPE 2 height30,000 cm
VPE 2 width30,000 cm
VPE 2 length40,000 cm
VPE 2 weight12,516 kg
VPE 3 typeP12
VPE 3 quantity56
VPE 3 height45,000 cm
VPE 3 width80,000 cm
VPE 3 length120,000 cm
VPE 3 weight112,128 kg
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1015855
qrcode für Schneider Electric LV516331 power circuit breaker 3P 36 kA