Additional features [Uimp] Rated impulse voltage withstand 8 kV corresponds to EN/IEC 60947-2 Network frequency 50/60 Hz Breaking capacity F [Ics] Rated operational breaking capacity 18 kA at 440 V AC 50/60 Hz according to IEC 60947-2; 36 kA at 380/415 V AC 50/60 Hz according to IEC 60947-2; 70 kA at 220/240 V AC 50/60 Hz according to IEC 60947-2 Neutral position Left Mechanical life 30,000 cycles Electrical lifetime 12000 cycles 415 V In corresponds to IEC 60947-2 Control type Toggle switch Adjustable range for thermal protection 56…80 A Neutral conductor protection setting 1 x Ir (4D) [Ir] type of long-time pickup setting Adjustable Adjustment range for long exposure 0,7 - 1 x In Type of long-time delay setting Fixed [Ii] type of instantaneous short-circuit setting Fixed Adjustment range of instantaneous short circuit 640 A Mounting bracket Rear panel Mounting mode Fixed Connection on top side front side Connection on underside front side Connections - terminals Screwed connection Terminal pitch 35 mm Compatibility code CVS100 Width 140 mm Depth 86 mm Height 161 mm Product weight 1,9 kg Contact position indicator Ja Contractual warranty Warranty (in months) 18 Main features Product series EasyPacT Product name EasyPacT CVS Device short name CVS100F Product or component type Power-cut-out switch Device application Distribution Pole description 4P Description of protected poles 4D Earth fault protection (Vigi Add On) None [In] Rated current 80 A at 40 °C Type of network AC Application category Category A Rated ultimate short-circuit breaking capacity [Icu] 36 kA Icu at 440 V AC 50/60 Hz, complies with IEC 60947-2; 36 kA Icu at 380/415 V AC 50/60 Hz, complies with IEC 60947-2; 70 kA Icu at 220/240 V AC 50/60 Hz, complies with IEC 60947-2 Trigger name TM-D Trigger technology Thermal-magnetic Trigger power 80 A at 40 °C Degree of protection Short-circuit protection (magnetic); overload protection (thermal) Mounting Standards EN 60947-2; IEC 60947-2 Product certifications GOST; IEC Protection class for electric shocks Class II Pollution degree 3 entspricht IEC 60664-1 Degree of protection (IP) IP40 Operating ambient temperature -25…70 °C Ambient temperature during storage -50…85 °C Packaging units VPE 1 type PCE Number of devices per package 1 VPE 1 height 13,500 cm VPE 1 width 14,500 cm VPE 1 length 19,000 cm Packaging weight (Lbs) 2,156 kg VPE 2 type S03 VPE 2 quantity 4 VPE 2 height 30,000 cm VPE 2 width 30,000 cm VPE 2 length 40,000 cm VPE 2 weight 9,044 kg VPE 3 type P12 VPE 3 quantity 32 VPE 3 height 45,000 cm VPE 3 width 80,000 cm VPE 3 length 120,000 cm VPE 3 weight 84,352 kg