| Complementary |
| Test function | Remote test; Remote test (via communication); Local |
| Signal contacts composition | 1 C/O alarm fail-safe; 1 NO pre-alarm fail-safe |
| Type of measurement | Earth fault current internal measurement, range: 20...200 %, accuracy: +/- 20 % |
| Refresh time | 0.5 s |
| Communication service | Modbus slave |
| Tamperproof of settings | Protected by access code |
| Wire stripping length | Alarm circuit: 6 mm; Relay test and fault reset: 6 mm; Sensor: 6 mm; Voltage presence: 6 mm; Power supply: 6 mm; Pre alarm: 6 mm |
| Tightening torque | Alarm circuit: 0.5 N.m; Relay test and fault reset: 0.5 N.m; Sensor: 0.5 N.m; Voltage presence: 0.5 N.m; Power supply: 0.5 N.m; Pre alarm: 0.5 N.m |
| Standards | EN/IEC 60947-2 Annex M; EN/IEC 60755 |
| Width | 72 mm |
| Height | 72 mm |
| Depth | 117 mm |
| Cut-out dimensions | 68 x 68 mm |
| Net weight | 0.3 kg |
| IP degree of protection | IP40 front face: conforming to IEC 60529; IP30 other parts: conforming to IEC 60529; IP20 connection: conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Mechanical robustness | Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52 |
| Overvoltage category | IV |
| Electrical shock protection class | Class II |
| Electromagnetic compatibility | Conducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IEC 61000-4-3 |
| Relative humidity | 95 % at 55 °C |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…55 °C |
| Ambient air temperature for storage | -40…85 °C |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | VigiPacT |
| Device short name | RHU |
| Product or component type | Residual current protection relay |
| Relay application | Monitoring relay; Protection relay |
| Mounting support | Front panel |
| Earth-leakage protection class | Type A |
| Type of setting | Modbus address; Keypad |
| Residual earth-leakage sensitity adjustment type | Adjustable |
| Earth-leakage sensitivity | 0.03…1 A, adjustable in step of 0.001 A; 1…30 A, adjustable in step of 0.1 A |
| Earth-leakage time delay | Instantaneous for 0.03 A; Adjustable 0…4.5 s for 0.03…30 A adjustable in step of 10 ms |
| Threshold setting | 0.015...1 A adjustable in step of 0.001 A pre-alarm; 1...30 A adjustable in step of 0.1 A pre-alarm; 0.03...1 A adjustable in step of 0.001 A alarm; 1...30 A adjustable in step of 0.1 A alarm |
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor; VigiPacT A earth leakage current sensor; VigiPacT L earth leakage current sensor |
| [Ithe] conventional enclosed thermal current | 8 A |
| Minimum load | 10 mA at 12 V |
| [Us] rated supply voltage | 220...240 V AC 50/60 Hz 70...110 % |
| Power consumption in VA | 8 VA |
| Monitored distribution system | 1000 V - AC at 50/60 Hz (maximum) ; 1000 V - AC at 400 Hz (maximum) |
| Earthing system | TT; TN-S; IT |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Reset | Remote reset |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.5 cm |
| Package 1 Width | 11.0 cm |
| Package 1 Length | 15.5 cm |
| Package 1 Weight | 430.0 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 40.0 cm |
| Package 2 Length | 60.0 cm |
| Package 2 Weight | 11.086 kg |
VigiPacT RHU is a communicating residual current device for front panel mounting. It protects against direct or indirect contact with people, fire hazards and motors. It measures the leakage current in an electrical installation through its associated toroidal transformer. It trips the associated circuit breaker when the set residual current is exceeded. It can trigger an alarm and a pre-alarm. The operating supply voltage is 220/240VAC 50/60Hz. It is a type A earth fault protection class. The current sensitivity is between 30 mA and 30 A. The time delay is adjustable from 0 to 4.5s. It is installed on a front panel and has an IP40 protection degree. It must be connected to a compatible Schneider Electric type A toroidal or rectangular sensor. It complies with IEC 60755, IEC 60947-2 Annex M and IEC 60947-5-1 standards. RUH is integrated into the Smart Panel architecture with Modbus communication.