Further information for Schneider Electric LV480801 connection flag M8 standard
Complementary
[Iq] Breaking capacity with fuses (kA RMS)
80 kA at 415 V (AC); 80 kA at 500 V (AC); 25 kA at 690 V (AC)
[Icw] rated short-time withstand current
5 kA for 1 s
[Icm] Rated short-circuit making capacity
7.65 kA at 690 V
Rated duty
Uninterrupted
Control type
Fuse carriers handle
Provision for padlocking
Lead seal
Mounting position
Vertical; Horizontal
Mounting mode
Fixed
Mounting support
Backplate
Mounting location
Side by side
Contact operation
Single-break
Mechanical durability
1600 cycles
Electrical durability
AC-21B: 200 cycles 690 V AC 50/60 Hz; AC-22B: 200 cycles 500 V AC 50/60 Hz; AC-23B: 200 cycles 415 V AC 50/60 Hz
Connections - terminals
M8 terminals
Tightening torque
5 N.m for terminal
Width
106 mm
Height
206 mm
Depth
80 mm
Net weight
0.6 kg
Standards
EN/IEC 60947-1; EN/IEC 60947-3
Product certifications
CE; CCC; EAC
Contractual warranty
Warranty (in months)
18
Environment
Electrical shock protection class
Class II front face
IP degree of protection
IP3x front face: conforming to IEC 60529
IK degree of protection
IK07 conforming to EN 50102
Pollution degree
3 conforming to IEC 60947
Ambient air temperature for operation
-20…70 °C
Ambient air temperature for storage
-50…85 °C
Logistical informations
Country of origin
DE
Main
Range
FuPacT
Product name
FuPacT ISFT
Device short name
ISFT160
Product or component type
Fuse-switch disconnector
Device application
Equipment protection, monitoring and control; Distribution
Signalling function
Separated fuse monitor
Poles description
3P
Number of fuse carriers
3
Fuse type
DIN
Fuse size
NH00
Suitability for isolation
Yes conforming to EN/IEC 60947-3
[Ith] conventional free air thermal current
160 A ( 40 °C ) power dissipation per fuse: 12 W
[Ithe] conventional enclosed thermal current
160 A at 40 °C, Power dissipation per fuse: 12 W
Maximum power dissipation per pole
15 W
[Ue] rated operational voltage
690 V AC 50/60 Hz; 440 V DC; 800 V AC 50/60 Hz AC-20; 800 V DC DC-20
[Ui] rated insulation voltage
1000 V AC 50/60 Hz; 1000 V DC
[Uimp] rated impulse withstand voltage
8 kV
[Ie] rated operational current
AC-21B: 160 A at 220/240 V AC 50/60 Hz; AC-21B: 160 A at 380/415 V AC 50/60 Hz; AC-21B: 160 A at 440/480 V AC 50/60 Hz; AC-21B: 160 A at 500 V AC 50/60 Hz; AC-21B: 160 A at 660/690 V AC 50/60 Hz; AC-22B: 160 A at 220/240 V AC 50/60 Hz; AC-22B: 160 A at 380/415 V AC 50/60 Hz; AC-22B: 160 A at 440/480 V AC 50/60 Hz; AC-22B: 160 A at 500 V AC 50/60 Hz; DC-21B: 160 A at 220 V DC (3 poles in series); DC-21B: 125 A at 440 V DC (3 poles in series); DC-22B: 160 A at 220 V DC (3 poles in series)