| Complementary |
| [Iq] Breaking capacity with fuses (kA RMS) | 80 kA at 415 V (AC); 80 kA at 500 V (AC); 25 kA at 690 V (AC) |
| [Icw] rated short-time withstand current | 3.6 kA for 1 s |
| [Icm] Rated short-circuit making capacity | 5.2 kA at 690 V |
| Rated duty | Uninterrupted |
| Control type | Fuse carriers handle |
| Provision for padlocking | Lead seal |
| Mounting position | Vertical; Horizontal |
| Mounting support | Backplate; Busbars; DIN rail with accessory |
| Mounting location | Side by side |
| Contact operation | Single-break |
| Mechanical durability | 2000 cycles |
| Electrical durability | AC-21B: 300 cycles 690 V AC 50/60 Hz; AC-22B: 300 cycles 500 V AC 50/60 Hz; AC-23B: 300 cycles 415 V AC 50/60 Hz |
| Connections - terminals | Cable connectors downstream 2.5…50 mm²; Cable connectors upstream 2.5…50 mm² |
| Tightening torque | 4.5 N.m for terminal |
| Width | 53 mm |
| Height | 216 mm |
| Depth | 80 mm |
| Net weight | 0.54 kg |
| Standards | EN/IEC 60947-1; EN/IEC 60947-3 |
| Product certifications | CE; CCC; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electrical shock protection class | Class II front face |
| IP degree of protection | IP3x front face: conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Pollution degree | 3 conforming to IEC 60947 |
| Ambient air temperature for operation | -20…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Main |
| Range | FuPacT |
| Product name | FuPacT ISFT |
| Device short name | ISFT100N |
| Product or component type | Fuse-switch disconnector |
| Device application | Distribution; Equipment protection, monitoring and control |
| Poles description | 3P |
| Number of fuse carriers | 3 |
| Fuse type | DIN |
| Fuse size | NH000 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-3 |
| [Ith] conventional free air thermal current | 100 A ( 40 °C ) power dissipation per fuse: 9 W |
| [Ithe] conventional enclosed thermal current | 100 A at 40 °C, Power dissipation per fuse: 9 W |
| Maximum power dissipation per pole | 11 W |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz; 440 V DC; 800 V AC 50/60 Hz AC-20; 800 V DC DC-20 |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz; 1000 V DC |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Visible break | |
| Contact position indicator | |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.000 cm |
| Package 1 Width | 14.500 cm |
| Package 1 Length | 24.000 cm |
| Package 1 Weight | 528.100 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.749 kg |